Analysis of Low Frequency Oscillation Using the Multi-Interval Parameter Estimation Method on a Rolling Blackout in the KEPCO System

被引:2
作者
Shim, Kwan-Shik [1 ]
Ahn, Seon-Ju [1 ]
Yun, Sang-Yun [1 ]
Choi, Joon-Ho [1 ]
机构
[1] Chonnam Natl Univ, Dept Elect Engn, Gwangju 500757, South Korea
关键词
low frequency oscillation; multiple time interval; parameter estimation; prediction error polynomial; rolling blackout; PRONY ANALYSIS; PSS DESIGN; IDENTIFICATION; STABILITY; SYNCHROPHASOR; PERFORMANCE;
D O I
10.3390/en10040484
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper describes a multiple time interval ("multi-interval") parameter estimation method. The multi-interval parameter estimation method estimates a parameter from a new multi-interval prediction error polynomial that can simultaneously consider multiple time intervals. The root of the multi-interval prediction error polynomial includes the effect on each time interval, and the important mode can be estimated by solving one polynomial for multiple time intervals or signals. The algorithm of the multi-interval parameter estimation method proposed in this paper is applied to the test function and the data measured from a PMU (phasor measurement unit) installed in the KEPCO (Korea Electric Power Corporation) system. The results confirm that the proposed multi-interval parameter estimation method accurately and reliably estimates important parameters.
引用
收藏
页数:18
相关论文
共 29 条
[1]  
[Anonymous], 1991, STAT SIGNAL PROCESSI
[2]   TIME-SERIES IDENTIFICATION OF INTERAREA AND LOCAL GENERATOR RESONANT MODES [J].
BOLLINGER, KE ;
NORUM, WE .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (01) :273-279
[3]   Adaptive Wide-Area Damping Control Scheme for Smart Grids with Consideration of Signal Time Delay [J].
Cai, Guowei ;
Yang, Deyou ;
Liu, Cheng .
ENERGIES, 2013, 6 (09) :4841-4858
[4]  
Electric Power Research Institute, 1993, TR101850 EPRI
[5]   COMPARISON OF PRONY AND EIGENANALYSIS FOR POWER-SYSTEM CONTROL DESIGN [J].
GRUND, CE ;
PASERBA, JJ ;
HAUER, JF ;
NILSSON, S .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (03) :964-971
[6]   Practical robust PSS design through identification of low-order transfer functions [J].
Hasanovic, A ;
Feliachi, A ;
Hasanovic, A ;
Bhatt, NB ;
DeGroff, AG .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2004, 19 (03) :1492-1500
[7]   APPLICATION OF PRONY ANALYSIS TO THE DETERMINATION OF MODAL CONTENT AND EQUIVALENT MODELS FOR MEASURED POWER-SYSTEM RESPONSE [J].
HAUER, JF .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (03) :1062-1068
[8]   INITIAL RESULTS IN PRONY ANALYSIS OF POWER-SYSTEM RESPONSE SIGNALS [J].
HAUER, JF ;
DEMEURE, CJ ;
SCHARF, LL .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (01) :80-89
[9]   A TIME-DOMAIN APPROACH TO TRANSMISSION NETWORK EQUIVALENTS VIA PRONY ANALYSIS FOR ELECTROMAGNETIC TRANSIENTS ANALYSIS [J].
HONG, JH ;
PARK, JK .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (04) :1789-1797
[10]  
Johnson MA, 2000, 2000 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-4, P1918, DOI 10.1109/PESS.2000.868827