On-Site Diagnostic Tests on Medium Voltage, XLPE-Insulated Power Cables

被引:0
|
作者
Abou Dakka, Mahmoud [1 ]
Bulinski, Alexander [1 ]
Bamji, Soli [1 ]
机构
[1] Natl Res Council Canada, Ottawa, ON K1A 0R6, Canada
关键词
diagnostic measurements; medium voltage underground distribution cable; cross-linked polyethylene (XLPE); dissipation factor; dc depolarization current;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The dc depolarization current measurement technique was used to test 20 medium voltage, underground XLPE-insulated cables In the local utility power distribution network between January and March 2006 and then in March 2007. The cables varied in length (30 m to similar to 1600 m), voltage rating (9 to 28 kV), and age (4 to 36 years). Unlike a typical depolarization current measurement where only a low frequency portion of the current Is monitored with an electrometer, the described measurements have also included the high frequency component of the depolarization current, occurring right after switching off the poling voltage. The measurements in 2007 also included the dielectric loss factor measurements between 10 mHz and 500 Hz on selected cables to correlate the tan delta values with the parameters of the depolarization currents. A reasonable correlation was found between cable age and other operating conditions and the depolarization current characteristics. A one year period between 2006 and 2007 produced noticeable changes in the depolartzation current characteristics for some cable and almost no change in others. No consistent time effect on the insulation of various cables could be identified.
引用
收藏
页码:3019 / 3024
页数:6
相关论文
共 50 条
  • [21] Stress induced electrochemical degradation of the inner semicon layer of XLPE-insulated cables and model samples
    Steinfeld, K
    Kalkner, W
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1998, 5 (05) : 774 - 778
  • [22] On-Site Diagnostic Technique for Smart Maintenance of Power Cables
    Abou-Dakka, Mahmoud
    Bulinski, Alexander
    Bamji, Soli S.
    2011 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING, 2011,
  • [23] Severe Degradation of the Conductor Screen of Service and Laboratory Aged Medium Voltage XLPE Insulated Cables
    Hvidsten, Sverre
    Kvande, Stine
    Ryen, Arve
    Larsen, Per Bjorn
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2009, 16 (01) : 155 - 161
  • [24] Numerical Study of CH4 Generation and Transport in XLPE-Insulated Cables in Continuous Vulcanization
    Ruslan, Mohd Fuad Anwari Che
    Youn, Dong Joon
    Aarons, Roshan
    Sun, Yabin
    Sun, Shuyu
    MATERIALS, 2020, 13 (13) : 1 - 21
  • [25] Thermal Reserves and Improvements in the Design of XLPE-Insulated Medium-Voltage Cable for use in Electricity Supply Boards.
    Wichmann, Helmut
    Brueggemann, Helgo
    Harjes, Bernd
    Kober, Hannemarie
    1600, (82):
  • [26] Retrofitting - New high voltage XLPE cables substituting paper-insulated power cables in steel pipes
    Bannach, D
    Kirchner, M
    Neubert, R
    IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (02) : 287 - 291
  • [27] Numerical Analysis of a Continuous Vulcanization Line to Enhance CH4 Reduction in XLPE-Insulated Cables
    Ruslan, Mohd Fuad Anwari Che
    Youn, Dong Joon
    Aarons, Roshan
    Sun, Yabin
    Sun, Shuyu
    MATERIALS, 2021, 14 (04) : 1 - 23
  • [28] Withstand voltage testing in combination with PD measurements of XLPE cables under damped alternating voltage on-site
    Sun Zhenquan
    Zhao Xuefeng
    Li Jisheng
    Li Yanming
    CEIDP: 2009 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2009, : 77 - 80
  • [29] Dielectric breakdown strength correlation with time-to-failure during wet aging of XLPE-insulated cables
    Walton, MD
    Bernstein, BS
    Thue, WA
    Smith, JT
    IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (03) : 750 - 755
  • [30] FAULT SECTION DETECTION SYSTEM FOR 275-KV XLPE-INSULATED CABLES WITH OPTICAL SENSING TECHNIQUE
    INOUE, N
    TSUNEKAGE, T
    SAKAI, S
    IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (03) : 1148 - 1155