On-Site Diagnostic Tests on Medium Voltage, XLPE-Insulated Power Cables

被引:0
|
作者
Abou Dakka, Mahmoud [1 ]
Bulinski, Alexander [1 ]
Bamji, Soli [1 ]
机构
[1] Natl Res Council Canada, Ottawa, ON K1A 0R6, Canada
关键词
diagnostic measurements; medium voltage underground distribution cable; cross-linked polyethylene (XLPE); dissipation factor; dc depolarization current;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The dc depolarization current measurement technique was used to test 20 medium voltage, underground XLPE-insulated cables In the local utility power distribution network between January and March 2006 and then in March 2007. The cables varied in length (30 m to similar to 1600 m), voltage rating (9 to 28 kV), and age (4 to 36 years). Unlike a typical depolarization current measurement where only a low frequency portion of the current Is monitored with an electrometer, the described measurements have also included the high frequency component of the depolarization current, occurring right after switching off the poling voltage. The measurements in 2007 also included the dielectric loss factor measurements between 10 mHz and 500 Hz on selected cables to correlate the tan delta values with the parameters of the depolarization currents. A reasonable correlation was found between cable age and other operating conditions and the depolarization current characteristics. A one year period between 2006 and 2007 produced noticeable changes in the depolartzation current characteristics for some cable and almost no change in others. No consistent time effect on the insulation of various cables could be identified.
引用
收藏
页码:3019 / 3024
页数:6
相关论文
共 50 条
  • [1] Electrical conductivity of medium voltage XLPE insulated cables
    Hestad, Oystein Leif
    Mauseth, Frank
    Kyte, Ruth Helene
    CONFERENCE RECORD OF THE 2012 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION (ISEI), 2012, : 376 - 380
  • [2] XLPE-Insulated Cables Temperature Monitoring for the Determination of Their Residual Life
    Pugach, V. N.
    Polyakov, D. A.
    Nikitin, Konstantin I.
    Yurchuk, D. A.
    2017 XI INTERNATIONAL IEEE SCIENTIFIC AND TECHNICAL CONFERENCE DYNAMICS OF SYSTEMS, MECHANISMS AND MACHINES (DYNAMICS), 2017,
  • [4] On-site Diagnostic Tests On Polymer Insulated Cables Using Depolarization Current Measurements
    Dakka, M. Abou
    Bulinski, A.
    Bamji, S.
    2007 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS, VOLS 1 AND 2, 2007, : 725 - 728
  • [5] The performance of strippable and bonded screened medium-voltage XLPE-insulated cables under long-term accelerated aging
    Al-Arainy, A.
    Malik, Nazar H.
    Qureshi, Mohammed Iqbal
    Al-Saati, Mohammed Nabih
    IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (02) : 744 - 751
  • [6] New watertight 10-20 kV XLPE-insulated cables
    Anon
    Sahko, 1988, 61 (06): : 51 - 52
  • [7] Experimental Investigation of the Effect of Transient Overvoltages on XLPE-Insulated HVDC Cables
    Diban, Bassel
    Mazzanti, Giovanni
    Mazzocchetti, Laura
    Seri, Paolo
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (04) : 1779 - 1786
  • [8] EXPERIENCE WITH HIGH VOLTAGE XLPE INSULATED POWER CABLES IN NORWAY.
    Bjorlow-Larsen, K.
    Holte, T.A.
    Larsen, P.B.
    Electrical communication, 1985, 59 (04): : 446 - 450
  • [9] Post-irradiation effect analysis on XLPE-insulated LV cables used in nuclear power plants
    Suraci, Simone Vincenzo
    Fabiani, Davide
    Li, Chuanyang
    2019 2ND INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE 2019), 2019, : 53 - 56
  • [10] ACCELERATED AGING OF EXTRUDED DIELECTRIC POWER-CABLES .2. LIFE TESTING OF 15 KV XLPE-INSULATED CABLES
    BERNSTEIN, BS
    THUE, WA
    WALTON, MD
    SMITH, JT
    IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (02) : 603 - 608