A New Approach to Low-Voltage Circuit Breaker Short-Circuit Selective Coordination

被引:0
作者
Larsen, Ed [1 ]
机构
[1] Sq D Schneider Elect, Cedar Rapids, IA 52404 USA
来源
CONFERENCE RECORD 2008 IEEE INDUSTRIAL & COMMERCIAL POWER SYSTEMS TECHNICAL CONFERENCE | 2008年
关键词
Circuit breakers; coordination; discrimination; fault currents; overcurrent protection; selective coordination; selectivity;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The expanded requirements in the 2005 NFC for selective coordination have prompted many engineers to question if selective coordination can be achieved with low-voltage circuit breakers. This is a valid question as the time-current curves of low-voltage circuit breakers often suggest that coordination can only be achieved in the overload and low level fault current zones. Therefore, how time-current curves are developed and their limitations are discussed. A new way for system designers to evaluate the level of selective coordination between low-voltage circuit breakers is introduced, indicating that higher levels of coordination can be achieved than those shown by the use of time-current curves alone.
引用
收藏
页码:130 / 136
页数:7
相关论文
共 8 条
[1]  
*EAT EL, SEL COORD
[2]  
*GE, GE OV DEV INST SEL T
[3]  
*IEEE, 2422001 IEEE, P5
[4]  
International Organization for Standardization, 2007, 664722007 ISO, P10
[5]  
*NAT FIR PROT ASS, 2005, NAT EL COD, P27
[6]  
*UND LAB, 2006, UL 489 MOLD CAS CIRC, P48
[7]  
SELECTIVITY GUIDELIN
[8]  
SHORT CIRCUIT SELECT, P6