Entropy parameters for falling film absorber optimization

被引:17
作者
Giannetti, Niccolo [1 ]
Rocchetti, Andrea [2 ]
Lubis, Arnas [1 ]
Saito, Kiyoshi [1 ]
Yamaguchi, Seiichi [1 ]
机构
[1] Waseda Univ, Dept Appl Mech & Aerosp Engn, Shinjuku Ku, Tokyo 1698555, Japan
[2] DIEF, I-50139 Florence, Italy
关键词
Entropy generation; Irreversibility; Falling film; Absorber; Horizontal tube; Optimization; ABSORPTION-REFRIGERATION SYSTEMS; HEAT-EXCHANGER DESIGN; MASS-TRANSFER; EXERGY ANALYSIS; COOLING CYCLES; GENERATION; FLOW; MINIMIZATION; TEMPERATURE; PERFORMANCE;
D O I
10.1016/j.applthermaleng.2015.10.049
中图分类号
O414.1 [热力学];
学科分类号
摘要
A local entropy generation analysis, for water vapor absorption in LiBr-H2O solution, is performed referring to velocity, temperature and concentration fields obtained from the numerical solution of mass and energy transport equations. The hydrodynamic description is based on Nusselt boundary layer assumption and the actual amount of irreversibility introduced is determined for an absorptive falling film over a cooled horizontal tube inside the absorber. Results are explored in different operative conditions in order to examine the impact of the various irreversibility sources in a wide operative range. A least irreversible solution mass flow-rate can always be identified. Furthermore, a simple and general thermodynamic analysis, carried out regarding a refrigerating and a heat boosting applications, makes evidence of a dimensionless group "Q/sigma T" that separates the weight of the irreversibilities and gives the way to an optimization criterion applied to the absorber in order to improve the whole system efficiency. Both thermodynamic equilibrium and sub-cooling conditions of the solution at the inlet are considered for typical temperature and concentration of refrigerators' absorbers and heat transformers' absorbers. Results suggest the importance to work at reduced mass flow-rates with a thin uniform film. In practice, tension-active additives are required to realize this condition. Also, it is highlighted that the two parameters defined with reference to the dimensionless group "Q/sigma T" can be maximized by specific values of the tube radius, operative Reynolds number, solution sub-cooling and temperature difference between the wall and the inlet solution. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:750 / 762
页数:13
相关论文
共 38 条
[1]  
Andberg J., 1987, ASHRAE T, V93, P2454
[2]  
[Anonymous], HEAT FLUID FLOW
[3]  
[Anonymous], J HEAT TRANSFER T AS
[4]   An overview of combined absorption power and cooling cycles [J].
Ayou, Dereje S. ;
Caries Bruno, Joan ;
Saravanan, Rajagopal ;
Coronas, Alberto .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 21 :728-748
[5]   Characteristics of heat and mass transfer in vapor absorption of falling film flow on a horizontal tube [J].
Babadi, F ;
Farhanieh, B .
INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2005, 32 (09) :1253-1265
[6]   Mathematical modelling of a LiBr-H2O absorption chiller including two-dimensional distributions of temperature and concentration fields for heat and mass exchangers [J].
Banasiak, Krzysztof ;
Koziol, Joachim .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2009, 48 (09) :1755-1764
[7]   2ND LAW ANALYSIS OF COMBINED HEAT AND MASS-TRANSFER IN INTERNAL AND EXTERNAL FLOWS [J].
CARRINGTON, CG ;
SUN, ZF .
INTERNATIONAL JOURNAL OF HEAT AND FLUID FLOW, 1992, 13 (01) :65-70
[8]   Entropy generation in gas absorption into a falling liquid film [J].
Chermiti, Imen ;
Hidouri, Nejib ;
Ben Brahim, Ammar .
MECHANICS RESEARCH COMMUNICATIONS, 2011, 38 (08) :586-593
[9]  
CHOUDHURY SK, 1993, ASHRAE TRAN, V99, P81
[10]  
DiGuilio R.M:, 1990, ASHRAE T, V96