Removal of PCBs from electrical equipment by the vacuum heating separation method (Part. 1) removal of low concentration PCBs from pole transformers

被引:0
|
作者
Kanbe, H [1 ]
Shibuya, M [1 ]
机构
[1] Cent Res Inst Elect Power Ind, Tokyo 201, Japan
来源
2001 POWER ENGINEERING SOCIETY SUMMER MEETING, VOLS 1-3, CONFERENCE PROCEEDINGS | 2001年
关键词
PCBs; polychlorinated biphenyl; pole transformer; transformer; vacuum heating separation method; vacuum thermal recycling; VTR; Electrical Equipment;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
There are currently about four million pole transformers that were used for electric power supply throughout Japan that contain trace amounts (50mg-PCB/kg-insulation oil or less) of PCBs. The prompt creation of a safe disposal method to render this PCBs harmless is required. We performed tests on the removal of PCBs by a low temperature vacuum heating method, using pole transformers that had actually been placed in service and that contain low concentrations of PCBs. The results of these tests confirmed that under standard applicable conditions of a vacuum of 0.05 torr or less, a heating temperature of 200degreesC and a vacuum holding period of 10 hours, the residual quantity of PCBs in impregnated transformer parts can be almost reduced to less than the quantitative determination lower limit of 0.05mg-PCB/kg-material. The test results also clearly showed that the test equipment and the disposal method do not have a harmful effect on the environment.
引用
收藏
页码:1869 / 1874
页数:4
相关论文
共 4 条
  • [1] Removal of PCBs by vacuum heating separation: Removal process of PCBs by vacuum heating separation using a vibration dryer
    Tanaka, R
    Kobayashi, N
    Itaya, Y
    Mori, S
    Mizutani, E
    KAGAKU KOGAKU RONBUNSHU, 2004, 30 (05) : 679 - 684
  • [2] Proving test on removal of PCB from pole transformer by vacuum heating separation method
    Shibuya, M
    Kanbe, H
    Seki, T
    ELECTRICAL ENGINEERING IN JAPAN, 1997, 120 (03) : 17 - 28
  • [3] Removal of PCBs from PCB polluted sludge using the vacuum thermal recycling process
    Ohbayashi, H
    Takahashi, Y
    Hosomi, M
    KAGAKU KOGAKU RONBUNSHU, 2002, 28 (03) : 363 - 367
  • [4] Removal of insulation oil from a pole transformer by vacuum heating separation using a vibration dryer
    Tanaka, R
    Kobayashi, N
    Itaya, Y
    Mori, S
    Tachi, Y
    Hayashi, Y
    Mizutani, E
    KAGAKU KOGAKU RONBUNSHU, 2004, 30 (04) : 440 - 446