Applying Intelligent Fast Load Shed Using IEC 61850 GOOSE

被引:0
|
作者
Theron, J. C. [1 ]
Wilsey, Troy [2 ]
Colonnese, Anthony [2 ]
Gagner, Russell [3 ]
机构
[1] GE Grid Solut, 650 Markland St, Markham, ON L6C 0M1, Canada
[2] Ameresco, 111 Speen St,Ste 410, Framingham, MA 01701 USA
[3] Naval Facil Engn Command, Portsmouth Naval Shipyard, Bldg 43,PWD Maine, Kittery, ME 03904 USA
来源
2018 71ST ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS (CPRE) | 2018年
关键词
Fast Load Shed (FLS); GOOSE (Generic Object Oriented Substation Event); Quality of Service (QoS); Fast Load Shed Controller (FLSC); Fast Load Shed Aggregator (FLSA); IED (Intelligent Electronic Device); Rate of Change of Frequency (ROCOF); HMI (Human Machine Interface); DCS (Distributed Control System); Infeed; Load Group;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Industrial facilities with co-generation are in critical need of load shedding to prevent collapse of the cogeneration assets. Load shedding should be sub-cycle speed to manage thousands of distributed loads within a facility. This paper describes the capabilities of such a fast load shedding scheme spanning across a wide array of relays provided by various vendors and potentially a large quantity, and a case study system and experience of applying such a system. The fast load shed scheme described in this paper utilizes a proven system and makes it easy to configure larger and more complex load shed schemes-The paper describes the proposed architecture of a centralized fast load shed controller-based scheme interfaced with local generator/feeder/transformer/motor protection relays over IEC 61850 GOOSE A major challenge of such a large-scale load shed scheme deployment is the configuration of devices, especially the IEC 61850 GOOSE engineering process which may add further complexity. This paper also discusses IEC 61850 GOOSE scheme configuration with high-speed performance requirements-Lessons teamed from the case study fast load shed scheme deployment, testing and operations are also discussed.
引用
收藏
页数:9
相关论文
共 50 条
  • [11] IEC-61850 GOOSE TRAFFIC MODELING AND GENERATION
    Hegazi, Omar
    Hammad, Eman
    Farraj, Abdallah
    Kundur, Deepa
    2017 IEEE GLOBAL CONFERENCE ON SIGNAL AND INFORMATION PROCESSING (GLOBALSIP 2017), 2017, : 1100 - 1104
  • [12] A Practical Guide of Troubleshooting IEC 61850 GOOSE Communication
    Huang, Wei
    2018 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2018,
  • [13] Safety related functions with IEC 61850 GOOSE messaging
    Magro, Micaela Caserza
    Pinceti, Paolo
    Rocca, Luca
    Rossi, Giorgio
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 104 : 515 - 523
  • [14] A Practical Guide of Troubleshooting IEC 61850 GOOSE Communication
    Huang, Wei
    2017 70TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS (CPRE), 2017,
  • [15] GOOSE performance assessment on an IEC 61850 redundant network
    Essa, Mohamed Hosny Tawfeek
    Crossley, Peter
    JOURNAL OF ENGINEERING-JOE, 2018, (15): : 841 - 845
  • [16] Modeling of IEC 61850 GOOSE Substation Communication Traffic Using ARMA Model
    Feizimirkhani, Ronak
    Bratcu, Antoneta Iuliana
    Besanger, Yvon
    Labonne, Antoine
    Braconnier, Thierry
    PROCEEDINGS OF 2019 IEEE PES INNOVATIVE SMART GRID TECHNOLOGIES EUROPE (ISGT-EUROPE), 2019,
  • [17] A study on GOOSE communication based on IEC 61850 using MMS Ease Lite
    Nguyen-Dinh, Nhat
    Kim, Gwan-Su
    Lee, Hong-Hee
    2007 INTERNATIONAL CONFERENCE ON CONTROL, AUTOMATION AND SYSTEMS, VOLS 1-6, 2007, : 715 - 719
  • [18] Implementation of Arc-Flash Protection Using IEC 61850 Goose Messaging
    Cabrera, Charina
    Chiu, Stephen
    Nair, Nirmal Kumar C.
    2012 IEEE INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2012,
  • [19] Practical Considerations of Applying IEC61850 GOOSE Based Zone Selective Interlocking Scheme in Industrial Applications
    Zhao, Tony
    Sevov, Lubomir
    2013 66TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS, 2013, : 263 - 270
  • [20] Fault Location, Isolation, and Service Restoration (FLISR) Technique using IEC 61850 GOOSE
    Parikh, Palak
    Voloh, Ilia
    Mahony, Michael
    2013 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PES), 2013,