Prediction Model on Room Temperature Side Effect due to FastADR Aggregation for a Cluster of Building Air-Conditioning Facilities

被引:3
|
作者
Naramura, Taku [1 ]
Morikawa, Junji [3 ]
Ninagawa, Chuzo [2 ]
机构
[1] Gifu Univ, Dept Elect & Elect Engn, Grad Sch Engn, Gifu, Japan
[2] Gifu Univ, Dept Elect Elect & Comp Engn, Fac Engn, Gifu, Japan
[3] Mitsubishi Heavy Ind Co Ltd, Tokyo, Japan
关键词
neural network; auto regression; smart grid; demand response; building air-conditioning;
D O I
10.1002/eej.22946
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, we have constructed an auto regressive and neural network combined type prediction model for responsive change in the room temperature trend due to the fast automated demand response (FastADR) power limitation of office building air-conditioning facilities. We defined the average of differences between room temperature and set point of each indoor unit for the entire building as a FastADR side effect index for the building. Prediction experiments using an actual office building showed that the root mean square prediction error of our model was 0.23 degrees C for 5 min after the FastADR. This prediction ability is considered sufficient to estimate the side effect of FastADR power limitation.
引用
收藏
页码:17 / 25
页数:9
相关论文
共 11 条
  • [1] Averaging effect on stochastic response prediction in FastADR aggregation for building air-conditioning facilities
    Kondo, Shinji
    Morikawa, Junji
    Ninagawa, Chuzo
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2016, 11 (06) : 820 - 822
  • [2] Wide area network discrete feedback control on FastADR of a cluster of building air-conditioning facilities
    Kiyota, Akihisa
    Takahama, Morio
    Ninagawa, Chuzo
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2016, 11 (06) : 826 - 828
  • [3] Estimation on averaging effect of large-scale aggregation of DR transient responses of building multi air-conditioning facilities
    Suzuki K.
    Ninagawa C.
    Morikawa J.
    Inaba T.
    Kondo S.
    IEEJ Transactions on Power and Energy, 2018, 138 (07) : 582 - 590
  • [4] Estimation on averaging effect of large-scale aggregation of DR transient responses of building multi air-conditioning facilities
    Suzuki, Keita
    Ninagawa, Chuzo
    Morikawa, Junji
    Inaba, Takashi
    Kondo, Seiji
    ELECTRICAL ENGINEERING IN JAPAN, 2019, 206 (01) : 22 - 31
  • [5] A novel forecast method for air-conditioning load of public building considering accumulated temperature effect
    School of Electrical Engineering, Southeast University, Nanjing
    210096, China
    不详
    Open Electr. Electron. Eng. J., 1 (363-367):
  • [6] Remote Monitoring Integrated State Variables for AR Model Prediction of Daily Total Building Air-Conditioning Power Consumption
    Ninagawa, Chuzo
    Sato, Tomotaka
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2010, 5 (05) : 611 - 612
  • [7] Influence of air-conditioning waste heat on air temperature in Tokyo during summer: Numerical experiments using an urban canopy model coupled with a building energy model
    Ohashi, Yukitaka
    Genchi, Yutaka
    Kondo, Hiroaki
    Kikegawa, Yukihiro
    Yoshikado, Hiroshi
    Hirano, Yujiro
    JOURNAL OF APPLIED METEOROLOGY AND CLIMATOLOGY, 2007, 46 (01) : 66 - 81
  • [8] Complex Coordination Control with Entire Power Limitation and Partial Temperature Priority of Building-Multi Air-conditioning Facilities for Real-Time Pricing
    Aoki, Yoshifumi
    Ito, Hiromichi
    Ninagawa, Chuzo
    Morikawa, Junji
    Inaba, Takashi
    Kondo, Seiji
    IEEJ JOURNAL OF INDUSTRY APPLICATIONS, 2019, 8 (03) : 566 - 575
  • [9] An advanced simulation test bed for the stability analysis of variable air volume air-conditioning control system. Part 1: Optimal simplified model of building envelope for room thermal performance prediction
    Yi, Zhi-Ming
    Yu, Hang
    Wei, Qi
    Chu, Xiang-Yang
    ENERGY AND BUILDINGS, 2018, 158 : 950 - 963
  • [10] Dynamic room temperature setpoints of air-conditioning demand response based on heat balance equations with thermal comfort model as constraint: On-site experiment and simulation
    Li, Zeyang
    Meng, Qinglong
    Wei, Ying'an
    Zhang, Liang
    Sun, Zhe
    Lei, Yu
    Yang, Li
    Yan, Xiuying
    JOURNAL OF BUILDING ENGINEERING, 2023, 65