Influence of remote earth and impulse polarity on earthing systems by field measurement

被引:1
作者
Abdullah, Syarifah [1 ]
Nor, Normiza Mohamad [1 ]
Agbor, Nkwa [1 ]
Reffin, Muhd [1 ]
Othman, Marinah [2 ]
机构
[1] Multimedia Univ, Fac Engn, Persiaran Multimedia, Cyberjaya 63100, Malaysia
[2] Univ Sains Islam Malaysia, Fac Engn & Built Environm, Nilai 71800, Negeri Sembilan, Malaysia
关键词
earthing; electrodes; impulse testing; electric resistance measurement; voltage measurement; electric current measurement; remote earth location; earthing system; field measurement; grounding system; return electrode location; earthing electrode; circular electrode; impulse resistance measurement; positive impulse polarity; distance; 80; m; GROUNDING SYSTEMS; ELECTRODES; BEHAVIOR; DISCHARGES; SAND;
D O I
10.1049/iet-smt.2017.0092
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
There has been a vast vacuum in the literature on the importance of the location of remote earth carried out during impulse test on grounding systems using field measurements. Some published work show that the remote earth is installed surrounding the electrode under tests, whilst some have used separate remote earth, away from it. This work studies the impact of return electrode location on transient behaviour of the earthing electrode. The electrode under test is a single rod. Two types of remote earth configurations are used, a circular electrode with multiple rods surrounding the single rod, and one that is 80m away from it. Impulse tests are conducted under both impulse polarities. Voltage and current traces are captured for a single rod, using two different types of remote earth configurations, with the impulse resistance measured as well. It has been established that the arrangement of the remote earth poses no influence on the test results. That said, higher oscillations of current traces and higher resistance values have been observed in negative impulse in comparison with positive impulse polarities.
引用
收藏
页码:308 / 313
页数:6
相关论文
共 20 条
  • [1] Experimental study on transient impedance of grounding rods encased in ground enhancing compounds
    Androvitsaneas, Vasilios P.
    Gonos, Ioannis F.
    Stathopulos, Ioannis A.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2016, 139 : 109 - 115
  • [2] [Anonymous], 2012, 812012 ANSIIEEE
  • [3] Bellaschi P.L., 1943, AIEE T, V62, P334
  • [4] CABRERA VM, 1993, J ELECTROSTAT, V30, P17
  • [5] CABRERA VM, 1993, J ELECTROSTAT, V30, P47
  • [6] The influence of seasonal soil moisture on the behavior of soil resistivity and power distribution grounding systems
    Coelho, Vilson Luiz
    Piantini, Alexandre
    Almaguer, Hugo A. D.
    Coelho, Rafael A.
    Boaventura, Wallace do C.
    Paulino, Jose Osvaldo S.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2015, 118 : 76 - 82
  • [7] NONLINEAR BEHAVIOR OF GROUND ELECTRODES UNDER LIGHTNING SURGE CURRENTS - COMPUTER MODELING AND COMPARISON WITH EXPERIMENTAL RESULTS
    GERI, A
    VECA, GM
    GARBAGNATI, E
    SARTORIO, G
    [J]. IEEE TRANSACTIONS ON MAGNETICS, 1992, 28 (02) : 1442 - 1445
  • [8] Haddad A., 2010, 2010 International Conference on High Voltage Engineering and Application (ICHVE 2010), P469, DOI 10.1109/ICHVE.2010.5640724
  • [9] On the Analysis of Impulse Test Results on Grounding Systems
    Harid, N.
    Griffiths, H.
    Mousa, S.
    Clark, D.
    Robson, S.
    Haddad, A.
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2015, 51 (06) : 5324 - 5334
  • [10] Harid N., 2011, 2011 7th Asia-Pacific International Conference on Lightning (APL 2011), P686, DOI 10.1109/APL.2011.6110214