Experimental study of a novel integrated system of indirect evaporative cooler with internal baffles and evaporative condenser

被引:43
|
作者
Kabeel, A. E. [1 ]
Bassuoni, M. M. [1 ,2 ]
Abdelgaied, Mohamed [1 ]
机构
[1] Tanta Univ, Fac Engn, Dept Power Mech Engn, Tanta, Egypt
[2] Taif Univ, Fac Engn, Dept Mech Engn, POB 888, Al Haweiah 21974, Saudi Arabia
关键词
Experimental work; Indirect evaporative cooler; Evaporative condenser; Cross flow heat exchanger; Baffle plate; Cooling load; MASS-TRANSFER PROCESSES; HEAT-EXCHANGERS; COOLING PERFORMANCE; AIR-CONDITIONER; MODEL; FLOW;
D O I
10.1016/j.enconman.2017.02.025
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, the performance of a novel integrated system of indirect evaporative cooler with internal baffles as air pre-cooling unit and evaporative condenser has been experimentally investigated. For this purpose, the experimental setup consisting of an indirect evaporative cooler with internal baffles followed by an evaporative condenser contains the hot water serpentine tubes with external thin film cotton layer was designed, constructed and tested. The influences of pre-cooling unit and the external thin film cotton layer on the performance of the evaporative condenser are investigated. The experimental results show that, for increasing the air flow rate from 250 to 1450 m(3)/h, the temperature difference of hot water through the evaporative condenser change in the ranges between 13 and 24.9 degrees C for the case without pre-cooling unit, 17.6-38.4 degrees C for using the pre-cooling unit with internal baffles and with use the thin film cotton layer. Also, the rate of change of the cooling load is in the ranges between 166 and 318 kW for case without pre-cooling unit, but for using the pre-cooling unit with internal baffles and with use the thin film cotton layer the cooling load change between 224.7 and 4903 kW. For using the external thin film cotton layer on the tubes of cross flow heat exchanger and with use the pre-cooling unit with internal baffles before the evaporative condenser the percentage increases in the cooling load change between 35.4 and 54.2% compared to the evaporative condenser without pre-cooling unit. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:518 / 525
页数:8
相关论文
共 50 条
  • [1] Numerical and experimental investigation of a novel configuration of indirect evaporative cooler with internal baffles
    Kabeel, A. E.
    Abdelgaied, Mohamed
    ENERGY CONVERSION AND MANAGEMENT, 2016, 126 : 526 - 536
  • [2] Experimental and Numerical Study on Performance of Indirect Evaporative Cooler with Baffles
    Kim, Seong-Bhin
    Moon, Kwang-Am
    Choi, Hwi-Ung
    Choi, Kwang-Hwan
    HEAT TRANSFER ENGINEERING, 2025,
  • [3] Experimental study of a novel indirect evaporative cooler
    Wang, Yugang
    Liu, Jiaping
    Xiang, Huang
    CONSTRUCTION AND URBAN PLANNING, PTS 1-4, 2013, 671-674 : 2547 - +
  • [4] Modeling and experimental study of an indirect evaporative cooler
    De Antonellis, Stefano
    Joppolo, Cesare Maria
    Liberati, Paolo
    Milani, Samanta
    Romano, Francesco
    ENERGY AND BUILDINGS, 2017, 142 : 147 - 157
  • [5] A novel integrated system of ground heat exchanger and indirect evaporative cooler
    Khalajzadeh, Vahid
    Farmahini-Farahani, Moien
    Heidarinejad, Ghassem
    ENERGY AND BUILDINGS, 2012, 49 : 604 - 610
  • [6] Theoretical and experimental study on the tubular indirect evaporative cooler
    Huang, Xiang
    Wang, Yugang
    Wu, Junmei
    PROCEEDINGS OF THE 3RD ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING VOLS I AND II, 2006, : 263 - +
  • [7] An experimental study on condensate film of indirect evaporative cooler
    Lv, Jian
    Meng, Dandong
    Chen, Yi
    You, Yuwen
    Li, Han
    INNOVATIVE SOLUTIONS FOR ENERGY TRANSITIONS, 2019, 158 : 5753 - 5758
  • [8] Comparative study of two different evaporative systems:: an indirect evaporative cooler and a semi-indirect ceramic evaporative cooler
    Martínez, FJR
    Gómez, EV
    Martín, RH
    Gutiérrez, JM
    Diez, FV
    ENERGY AND BUILDINGS, 2004, 36 (07) : 696 - 708
  • [9] An improved indirect evaporative cooler experimental investigation
    Shahzad, Muhammad Wakil
    Burhan, Muhammad
    Ybyraiymkul, Doskhan
    Oh, Seung Jin
    Ng, Kim Choon
    APPLIED ENERGY, 2019, 256
  • [10] Novel desiccant cooling system using indirect evaporative cooler
    Belding, WA
    Delmas, MPF