Unified Power Quality Conditioner With Advanced Dual Control for Performance Improvement of DFIG-Based Wind Farm

被引:79
作者
Yang, Ruo Huan [1 ]
Jin, Jian Xun [1 ]
机构
[1] Tianjin Univ, Sch Elect & Informat Engn, Tianjin 300072, Peoples R China
关键词
Doubly fed induction generators; Oscillators; Stator windings; Rotors; Reactive power; Power quality; Doubly fed induction generator (DFIG); wind energy conversion system (WECS); power quality conditioner; energy storage; dual control; FED INDUCTION GENERATOR; FAULT-RIDE-THROUGH; ENERGY-STORAGE; OUTPUT POWER; TURBINE; CAPABILITY; OPERATION; CONVERTER;
D O I
10.1109/TSTE.2020.2985161
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The weakness of low voltage ride-through capacity, power oscillations under asymmetrical fault and the instability of the output power are three major difficulties that need to be urgently addressed in the field of doubly fed induction generator (DFIG). To simultaneously deal with these issues, this article proposes a cost-effective energy storage device-based unified power quality conditioner (ESD-UPQC) to improve the low voltage ride through capability of the DFIG, suppress voltage oscillations under unbalanced faults and regulate DFIG output power during fluctuated wind speed conditions. A comprehensive protection scheme is carried out that the series side converter of the ESD-UPQC is controlled using dual control to suppress the post-fault voltage oscillations under transient conditions, while three advanced control targets are proposed for the parallel side converter aiming at regulating DFIG output power during wind gust, and suppress power oscillations during symmetrical and asymmetrical grid faults. Simulation results attest the feasibility of the proposed controller. The robustness of the proposed ESD-UPQC controller is validated through a series of comparisons based on a lead-acid battery scheme and an ESD-DFIG scheme for power smoothing and LVRT enhancement respectively.
引用
收藏
页码:116 / 126
页数:11
相关论文
共 32 条
[1]   Supercapacitor energy storage for wind energy applications [J].
Abbey, Chad ;
Joos, Geza .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2007, 43 (03) :769-776
[2]   Application of SMES Unit in Improving the Performance of an AC/DC Power System [J].
Abu-Siada, A. ;
Islam, Syed .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2011, 2 (02) :109-121
[3]  
[Anonymous], 2001, IEEE Power Engineering Review, V21, P10, DOI 10.1109/39.920961
[4]  
[Anonymous], 2011, Doubly Fed Induction Machine: Modeling and Control for Wind Energy Generation, DOI DOI 10.1002/9781118104965
[5]  
[Anonymous], 2015, 2015 INT C CIRC POW, DOI DOI 10.1109/ICCPCT.2015.7159410
[6]  
Chen X. Y., 2014, IEEE Trans Appl Supercond, V24
[7]   A Novel DVR-ESS-Embedded Wind-Energy Conversion System [J].
Chen, Xia ;
Yan, Linfang ;
Zhou, Xin ;
Sun, Haishun .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2018, 9 (03) :1265-1274
[8]   Enhancing Low-Voltage Ride-Through Capability and Smoothing Output Power of DFIG With a Superconducting Fault-Current Limiter-Magnetic Energy Storage System [J].
Guo, Wenyong ;
Xiao, Liye ;
Dai, Shaotao .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2012, 27 (02) :277-295
[9]   Scaled Current Tracking Control for Doubly Fed Induction Generator to Ride-Through Serious Grid Faults [J].
Huang, Qingjun ;
Zou, Xudong ;
Zhu, Donghai ;
Kang, Yong .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (03) :2150-2165
[10]   Optimal Superconducting Coil Integrated Into DFIG Wind Turbine for Fault Ride Through Capability Enhancement and Output Power Fluctuation Suppression [J].
Karaipoom, Tanapon ;
Ngamroo, Issarachai .