Faulty Feeder Identification and Fault Area Localization in Resonant Grounding System Based on Wavelet Packet and Bayesian Classifier

被引:0
作者
Chen, Jingwen [1 ]
Chu, Enliang [1 ]
Li, Yingchun [1 ]
Yun, Baoji [2 ]
Dang, Hongshe [1 ]
Yang, Yali [3 ]
机构
[1] Shaanxi Univ Sci & Technol, Power Syst Relay Protect Lab, Xian, Peoples R China
[2] Xian Xirui Control Technol Co Ltd, Xian, Peoples R China
[3] State Grid Shaanxi Elect Power Co Maintenance Co, Xian, Peoples R China
关键词
Resonant grounding system; single-phase earth fault; faulty feeder identification; fault area localization; wavelet packet; Bayesian classifier; TRANSMISSION-LINES; EARTH FAULT; LOCATION; INDICATORS; PROTECTION; SCHEME;
D O I
10.35833/mpce.2019.000051
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Accurate fault area localization is a challenging problem in resonant grounding systems (RGSs). Accordingly, this paper proposes a novel two-stage localization method for single-phase earth faults in RGSs. Firstly, a faulty feeder identification algorithm based on a Bayesian classifier is proposed. Three characteristic parameters of the RGS (the energy ratio, impedance factor, and energy spectrum entropy) are calculated based on the zero-sequence current (ZSC) of each feeder using wavelet packet transformations. Then, the values of three parameters are sent to a pre-trained Bayesian classifier to recognize the exact fault mode. With this result, the faulty feeder can be finally identified. To find the exact fault area on the faulty feeder, a localization method based on the similarity comparison of dominant frequency-band waveforms is proposed in an RGS equipped with feeder terminal units (FTUs). The FTUs can provide the information on the ZSC at their locations. Through wavelet-packet transformation, ZSC dominant frequency-band waveforms can be obtained at all FTU points. Similarities of the waveforms of characteristics at all FTU points are calculated and compared. The neighboring FTU points with the maximum diversity are the faulty sections finally determined. The proposed method exhibits higher accuracy in both faulty feeder identification and fault area localization compared to the previous methods. Finally, the effectiveness of the proposed method is validated by comparing simulation and experimental results.
引用
收藏
页码:760 / 767
页数:8
相关论文
共 38 条
  • [31] Yellagoud SK, 2016, INT J POWER ENERGY S, V36, P119, DOI 10.2316/Journal.203.2016.3.203-6245
  • [32] A Bayesian Approach for Fault Location in Medium Voltage Grids With Underground Cables
    Electrical Energy Systems Group, Eindhoven University of Technology, Eindhoven
    5612 AZ, Netherlands
    不详
    6812 AH, Netherlands
    [J]. IEEE Power Energy Technol. Syst. J., 4 (116-124):
  • [33] A Novel Single Phase Grounding Fault Protection Scheme Without Threshold Setting for Neutral Ineffectively Earthed Power Systems
    Zeng, Xiangjun
    Yu, Kun
    Wang, Yuanyuan
    Xu, Yao
    [J]. CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2016, 2 (03): : 73 - 81
  • [34] A fault locating method for multi-branch hybrid transmission lines in wind farm based on redundancy parameter estimation
    Zhang, Ke
    Zhu, Yongli
    Liu, Xuechun
    [J]. JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2019, 7 (05) : 1033 - 1043
  • [35] Flavonoids from the bran of Avena sativa
    Zhang Wei-Ku
    Xu Jie-Kun
    Zhang Li
    Du Guan-Hua
    [J]. CHINESE JOURNAL OF NATURAL MEDICINES, 2012, 10 (02) : 110 - 114
  • [36] Transmission line fault location for double phase-to-earth fault on non-direct-ground neutral system
    Zhang, Y
    Zhang, QC
    Song, WN
    Yu, YX
    Li, X
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (02) : 520 - 524
  • [37] Fault Analysis and Traveling-Wave Protection Scheme for Bipolar HVDC Lines
    Zhang, Ying
    Tai, Nengling
    Xu, Bin
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (03) : 1583 - 1591
  • [38] Zheng Guping, 2012, Proceedings of the CSEE, V32, P103