Personalized conditioning and its impact on thermal comfort and energy performance - A review

被引:223
作者
Vesely, Michal [1 ]
Zeiler, Wim [1 ]
机构
[1] Tech Univ Eindhoven, Dept Built Environm, NL-5600 MB Eindhoven, Netherlands
关键词
Cooling; Energy performance; Heating; Personalized conditioning; Task ambient conditioning; Thermal comfort; AIR-DISTRIBUTION SYSTEM; VENTILATION SYSTEM; HUMAN RESPONSE; GENDER-DIFFERENCES; SKIN TEMPERATURE; PARTIAL-BODY; MOVEMENT; HOT; SENSATION; CONJUNCTION;
D O I
10.1016/j.rser.2014.03.024
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The building industry nowadays is facing two major challenges - the increased concern for energy reduction and the growing need for comfort improvements. These challenges have led many researchers to develop a personalized conditioning system. Personalized conditioning aims to create a microclimate zone around a single workplace. In this way the energy is deployed only where it is actually needed, and the individual needs for thermal comfort are fulfilled. In recent years personalized conditioning has received a lot of attention in research publications. This paper reviews the impact of different personalized conditioning systems on thermal comfort and building energy performance. In the reviewed publications, it was demonstrated that thermal comfort can be well maintained at ambient temperatures that are 4-5 K higher as well as lower than the temperatures recommended by current standards. Personalized conditioning also allows reduction in energy consumption due to an increased cooling setpoint, a decreased heating setpoint, or a decreased ventilation rate of the background system. Energy simulations show that reductions of up to 60% can be achieved. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:401 / 408
页数:8
相关论文
共 77 条
  • [1] Thermal comfort and productivity - Evaluation of workplace environment in a task conditioned office
    Akimoto, Takashi
    Tanabe, Shin-ichi
    Yanai, Takashi
    Sasaki, Masato
    [J]. BUILDING AND ENVIRONMENT, 2010, 45 (01) : 45 - 50
  • [2] Thermal sensation and comfort with different task conditioning systems
    Amai, Hideyuki
    Tanabe, Shin-ichi
    Akimoto, Takashi
    Genma, Takeshi
    [J]. BUILDING AND ENVIRONMENT, 2007, 42 (12) : 3955 - 3964
  • [3] Human morphology and temperature regulation
    Anderson, GS
    [J]. INTERNATIONAL JOURNAL OF BIOMETEOROLOGY, 1999, 43 (03) : 99 - 109
  • [4] [Anonymous], 2013, ASHRAE Stand
  • [5] [Anonymous], 1970, THERMAL COMFORT ANAL
  • [6] A study of occupant cooling by personally controlled air movement
    Arens, E
    Xu, TF
    Miura, K
    Hui, Z
    Fountain, M
    Bauman, F
    [J]. ENERGY AND BUILDINGS, 1998, 27 (01) : 45 - 59
  • [7] Arens E, 2006, THERMAL AND MOISTURE TRANSPORT IN FIBROUS MATERIALS, P560, DOI 10.1533/9781845692261.3.560
  • [8] Arens E, 2006, J THERM BIOL, V31, P53, DOI 10.1016/j.jtherbio.2005.11.028
  • [9] Are 'class A' temperature requirements realistic or desirable?
    Arens, Edward
    Humphreys, Michael A.
    de Dear, Richard
    Zhang, Hui
    [J]. BUILDING AND ENVIRONMENT, 2010, 45 (01) : 4 - 10
  • [10] Bauman F.S., 1998, Build. Eng., V104, DOI DOI 10.1016/J.ENBUILD.2013.06.009