Conventional and advanced exergy analyses of an air-conditioning system in a subway station

被引:7
|
作者
Yin, Hua [1 ,2 ]
Guo, Huafang [1 ,2 ]
Tang, Zhihua [1 ,2 ]
Yu, Junyan [3 ]
Lu, Haiyang [4 ]
机构
[1] Chinese Acad Sci, Guangzhou Inst Energy Convers, Key Lab Renewable Energy, 2 Nengyuan Rd, Guangzhou 510640, Guangdong, Peoples R China
[2] Guangdong Key Lab New & Renewable Energy Res & De, 2 Nengyuan Rd, Guangzhou 510640, Guangdong, Peoples R China
[3] Guangzhou Metro Grp Co Ltd, Tower A,Wansheng Sq,1238 Xingang East Rd, Guangzhou 510330, Guangdong, Peoples R China
[4] Guangdong Univ Technol, Sch Automated Inst, Waihuan West Rd, Guangzhou 5100006, Guangdong, Peoples R China
关键词
conventional and advanced exergy analyses; air-conditioning system; subway station; CARBON-DIOXIDE; ENERGY; DESTRUCTIONS; OPTIMIZATION; PLANT; CYCLE; HVAC;
D O I
10.1504/IJEX.2019.100365
中图分类号
O414.1 [热力学];
学科分类号
摘要
Air-conditioning systems in subway stations consume a large amount of energy. In this study, conventional and advanced exergy analyses were carried out to determine the energy-saving potential of an air-conditioning system in a subway station. Results show that air handling unit (AHU) should be improved for the highest values of relative irreversibility (RI) with conventional exergy analysis, whereas the compressor should have the highest improvement priority for the largest avoidable exergy destruction with advanced exergy analysis. Moreover, influences of compressor efficiency, condensation temperature, and evaporation temperature on avoidable exergy destruction of the air-conditioning system were also investigated. According to the findings, compressor efficiency significantly influences the system's total avoidable exergy destruction. The lower the compressor efficiency, the more rapidly the avoidable exergy destruction of the compressor increases. Furthermore, the avoidable exergy destruction of condenser, compressor, cooling tower (CT), and cooling water pump (CWP) increases with the rise of the condensation temperature, whereas that of the evaporator, throttling valve (TV), condenser, compressor, CT, and CWP decreases with the rise of the evaporation temperature.
引用
收藏
页码:236 / 262
页数:27
相关论文
共 50 条
  • [1] Exergy and Thermoeconomic Analysis for an Underground Train Station Air-Conditioning Cooling System
    Liao, Ke Yang
    Chuah, Yew Khoy
    ENTROPY, 2016, 18 (03)
  • [2] Exergy and entransy analyses in air-conditioning system part 1-Similarity and distinction
    Zhang, Tao
    Liu, Xiaohua
    Tang, Haida
    Liu, Jun
    Jiang, Yi
    ENERGY AND BUILDINGS, 2016, 128 : 876 - 885
  • [3] Research on Subway Air-Conditioning System Design
    Chai, Zhi
    Nan, Jinrui
    Huang, Junkui
    INFORMATION TECHNOLOGY APPLICATIONS IN INDUSTRY II, PTS 1-4, 2013, 411-414 : 3039 - 3045
  • [4] Measurement analysis and load characteristics research on subway station ventilation and air-conditioning system
    Liu, Zhengning
    Wang, Wenqiang
    Sun, Chunhui
    Journal of Railway Science and Engineering, 2024, 21 (11) : 4746 - 4755
  • [5] Conventional and advanced exergy analyses of an underwater compressed air energy storage system
    Wang, Zhiwen
    Xiong, Wei
    Ting, David S. -K.
    Carriveau, Rupp
    Wang, Zuwen
    APPLIED ENERGY, 2016, 180 : 810 - 822
  • [6] Quantification on the Effects of Liquid-Vapor Separation in Air-Conditioning System by using Advanced Exergy Analysis
    Li, Yunhai
    Chen, Jianyong
    Lin, Xu
    Yang, Zhi
    Chen, Ying
    Luo, Xianglong
    JOURNAL OF THERMAL SCIENCE, 2020, 29 (03) : 597 - 608
  • [7] Operating optimization of air-conditioning water system in a subway station using data mining and dynamic system models
    Su, Xing
    Huang, Yixiang
    Wang, Lei
    Tian, Shaochen
    Luo, Yanping
    JOURNAL OF BUILDING ENGINEERING, 2021, 44
  • [8] Variable air volume air-conditioning experiment system with advanced controls
    Meng, Qinglong
    Yan, Xiuying
    Ren, Qingchang
    Adeli, Hojjat
    INDOOR AND BUILT ENVIRONMENT, 2016, 25 (01) : 114 - 127
  • [9] Air-conditioning Energy-saving Control Strategy at Subway Station Based on MAS Evolutionary Algorithm
    An Yanping
    Qian Ping
    PROCEEDINGS OF 8TH INTERNATIONAL CONFERENCE ON INTELLIGENT COMPUTATION TECHNOLOGY AND AUTOMATION (ICICTA 2015), 2015, : 122 - 125
  • [10] Air-conditioning load characteristics and grey box predicting model in subway stations
    Zhang, Huan
    Li, Zhuoran
    Fan, Xianwang
    Duan, Deyi
    Zheng, Wandong
    JOURNAL OF BUILDING ENGINEERING, 2024, 91