Analysis of control strategies for thermally activated building systems under demand side management mechanisms

被引:52
作者
Arteconi, A. [1 ]
Costola, D. [2 ]
Hoes, P. [2 ]
Hensen, J. L. M. [2 ]
机构
[1] Univ eCampus, I-22060 Novedrate, CO, Italy
[2] Eindhoven Univ Technol, Bldg Phys & Serv, NL-5600 MB Eindhoven, Netherlands
关键词
TABS; DSM; Control strategy; Load shifting; ENERGY; PERFORMANCE; SIMULATION; PROGRAMS; COMFORT; MODEL; COLD; TABS;
D O I
10.1016/j.enbuild.2014.05.053
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Thermally activated buildings systems (TABS) are systems that integrate heating/cooling devices in the building structure, so that the building elements act as thermal storage and have an active role in the energy supply and demand management. Although TABS are well known systems, there are still open questions in their realization, mainly concerning appropriate control strategies which are influenced by the large thermal inertia. The purpose of this paper is to analyze the influence of demand side management control strategies on the performance of a thermally activated building system applied in a commercial building. The goal is to estimate the potential of TABS for load shifting requested by the electricity grid. The analysis is performed by means of a sample case: first the existing TABS control strategy and then the possible implementation of DSM mechanisms are analyzed. In particular three different demand side management mechanisms are evaluated: (i) a peak shaving strategy, (ii)a random request of switching on/off the system and (iii) a night load shifting strategy. The simulation results show high potential of TABS within the DSM framework, since TABS allow load control while scarcely affect thermal comfort. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:384 / 393
页数:10
相关论文
共 28 条
[1]  
[Anonymous], 2013, ENERGY PRICE REPORT
[2]  
[Anonymous], 2010, ELECT J, DOI DOI 10.1016/J.TEJ.2009.12.007
[3]  
[Anonymous], TRNSYS MANUAL
[4]  
[Anonymous], 2013, DAY AHEAD MARKET HOU
[5]  
[Anonymous], IEEE T SUSTAINABLE E
[6]   State of the art of thermal storage for demand-side management [J].
Arteconi, A. ;
Hewitt, N. J. ;
Polonara, F. .
APPLIED ENERGY, 2012, 93 :371-389
[7]   A model predictive control optimization environment for real-time commercial building application [J].
Corbin, Charles D. ;
Henze, Gregor P. ;
May-Ostendorp, Peter .
JOURNAL OF BUILDING PERFORMANCE SIMULATION, 2013, 6 (03) :159-174
[8]   Hydronic circuit topologies for thermally activated building systems - design questions and case study [J].
de Wit, A. K. ;
Wisse, C. J. .
ENERGY AND BUILDINGS, 2012, 52 :56-67
[9]  
Dentel A., 2013, WP 5 MODEL SIMULATIO
[10]  
Faruqui A, 1992, PRINCIPLES PRACTICE