Interarea Oscillation Damping Using Active-Power Modulation of Multiterminal HVDC Transmissions

被引:69
作者
Harnefors, Lennart [1 ]
Johansson, Nicklas [1 ]
Zhang, Lidong [1 ]
Berggren, Bertil [1 ]
机构
[1] ABB, SE-72178 Vasteras, Sweden
关键词
HVDC; interarea oscillations; power oscillation damping; TIME-DELAY; AREA; CONTROLLER; DESIGN; SYSTEMS;
D O I
10.1109/TPWRS.2014.2306826
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Analytic investigations of interarea oscillation damping of an idealized two-machine system using active-power modulation of three-and four-terminal high-voltage dc (HVDC) transmissions are presented. It is shown that, generally, the pairing of two terminals gives the highest damping. Based on the analytical results, recommendations for how the pairing should be made are developed. Simulations, both on a two-machine system and on a more realistic 23-machine system, verify the analytical results.
引用
收藏
页码:2529 / 2538
页数:10
相关论文
共 35 条
[1]   Damping controller design for power system oscillations using global signals [J].
AboulEla, ME ;
Sallam, AA ;
McCalley, JD ;
Fouad, AA .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1996, 11 (02) :767-773
[2]  
Adapa R, 2012, IEEE POWER ENERGY M, V10, P18, DOI 10.1109/MPE.2012.2213011
[3]  
Ahmed N., 2012, 2012 IEEE 9th International Multi-Conference on Systems, Signals and Devices (SSD), DOI 10.1109/SSD.2012.6198119
[4]  
[Anonymous], IEEE POWER ENG REV
[5]  
[Anonymous], LONG TERM DYN PHAS 2
[6]  
[Anonymous], 2011, Power Electron. Appl. (EPE 2011)
[7]  
[Anonymous], P WIW 2013 12 INT WO
[8]  
[Anonymous], P EPRI HIGH VOLT DIR
[9]   DYNAMICS OF AC-DC SYSTEMS WITH CONTROLLED MULTI-TERMINAL HVDC TRANSMISSION [J].
CARTER, GK ;
GRUND, CE ;
HAPP, HH ;
POHL, RV .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (02) :402-413
[10]   Generalized Dynamic VSC MTDC Model for Power System Stability Studies [J].
Cole, Stijn ;
Beerten, Jef ;
Belmans, Ronnie .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2010, 25 (03) :1655-1662