Off-line coupled simulation method for transformer performance assessment under DC bias condition

被引:6
作者
Li, Jinlong [1 ]
Li, Jinzhong [1 ,2 ]
Li, Gang [1 ]
Hu, Xiaobo [3 ]
机构
[1] China Elect Power Res Inst, Beijing 100192, Peoples R China
[2] State Grid Corp China, Beijing 100031, Peoples R China
[3] Xian XD Transformer Co Ltd, Xian 710077, Shaanxi, Peoples R China
关键词
Transformer DC bias assessing; Off-line coupled simulation method (OCM); Transformer topological correct duality based transient model (TDTM); Multiphysics analysis; FINITE-ELEMENT SIMULATION; TRANSIENTS; 3-PHASE; MODEL;
D O I
10.1016/j.ijepes.2020.106462
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this short communication, we intend to introduce an off-line coupled simulation method (OCM) framework for the DC biased power transformer performance assessing. The OCM combined with the electromagnetic transient (EMT) and finite element method (FEM) simulation, which can benefit from fast calculating excitng current and deail representing the transformer's internal performance. It can be concluded from the numerical results of single-phase and three-phase transformers that it's feasible to estimate the transformer performance under DC bias condition with the proposed OCM framework, and it's quite promising in engineering application.
引用
收藏
页数:4
相关论文
共 22 条
[1]   Transient Thermal Analysis of an Eddy-Current Heated Conductor Applying FEM-DBCI [J].
Aiello, G. ;
Alfonzetti, S. ;
Dilettoso, E. ;
Salerno, N. .
IEEE TRANSACTIONS ON MAGNETICS, 2013, 49 (05) :1861-1864
[2]   Finite Element Analysis of Three-Phase Three-Limb Power Transformers Under DC Bias [J].
Biro, Oszkar ;
Koczka, Gergely ;
Leber, Gerald ;
Preis, Kurt ;
Wagner, Bernhard .
IEEE TRANSACTIONS ON MAGNETICS, 2014, 50 (02) :565-568
[3]   GIC observations and studies in the Hydro-Quebec power system [J].
Bolduc, L .
JOURNAL OF ATMOSPHERIC AND SOLAR-TERRESTRIAL PHYSICS, 2002, 64 (16) :1793-1802
[4]   A link between EMTP-RV and FLUX3D for transformer energization studies [J].
Dennetiere, S. ;
Guillot, Y. ;
Mahseredjian, J. ;
Rioual, M. .
ELECTRIC POWER SYSTEMS RESEARCH, 2009, 79 (03) :498-503
[5]  
Dular P, 2010, COMPEL, V29, P1444
[6]  
Kulkarni S.V., 2016, Transformer engineering: design, technology, and diagnostics
[7]   Core form transformer topological duality based transient model validation for exciting current calculation within DC bias [J].
Li, Jinlong ;
Li, Jinzhong .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (15) :3099-3107
[8]   Real-Time Finite-Element Simulation of Electromagnetic Transients of Transformer on FPGA [J].
Liu, Peng ;
Dinavahi, Venkata .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (04) :1991-2001
[9]  
Ngnegueu T, 2012, CIGRE SESS PAR, P1
[10]   Improvement of the Finite-Element Analysis of 3-D, Nonlinear, Periodic Eddy Current Problems Involving Voltage-Driven Coils Under DC Bias [J].
Plasser, Rene ;
Koczka, Gergely ;
Biro, Oszkar .
IEEE TRANSACTIONS ON MAGNETICS, 2018, 54 (03)