Fault Location Based on Synchronized Measurements: A Comprehensive Survey

被引:11
作者
Al-Mohammed, A. H. [1 ]
Abido, M. A. [2 ,3 ]
机构
[1] Saudi Elect Co, Dammam, Saudi Arabia
[2] King Fahd Univ Petr & Minerals, Dept Elect Engn, Dhahran 31261, Saudi Arabia
[3] Menoufia Univ, Dept Elect Engn, Fac Engn, Shibin Al Kawm, Egypt
关键词
COMBINED OVERHEAD LINE; TRANSMISSION-LINES; DETECTION/LOCATION TECHNIQUE; NUMERICAL ALGORITHM; PROTECTION SCHEME; PART II; VOLTAGE; DISCRIMINATION; SYSTEM; NETWORK;
D O I
10.1155/2014/845307
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
This paper presents a comprehensive survey on transmission and distribution fault location algorithms that utilize synchronized measurements. Algorithms based on two-end synchronized measurements and fault location algorithms on three-terminal and multiterminal lines are reviewed. Series capacitors equipped with metal oxide varistors (MOVs), when set on a transmission line, create certain problems for line fault locators and, therefore, fault location on series-compensated lines is discussed. The paper reports the work carried out on adaptive fault location algorithms aiming at achieving better fault location accuracy. Work associated with fault location on power system networks, although limited, is also summarized. Additionally, the nonstandard high-frequency-related fault location techniques based on wavelet transform are discussed. Finally, the paper highlights the area for future research.
引用
收藏
页数:10
相关论文
共 100 条
[1]   DEVELOPMENT OF A NEW FAULT LOCATION SYSTEM FOR MULTITERMINAL SINGLE TRANSMISSION-LINES [J].
ABE, M ;
OTSUZUKI, N .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (01) :159-168
[2]  
ABE M, 1994, PROCEEDINGS OF THE 1994 IEEE POWER ENGINEERING SOCIETY TRANSMISSION AND DISTRIBUTION CONFERENCE, P259, DOI 10.1109/TDC.1994.328390
[3]  
AGGARWAL RK, 1993, IEE CONF PUBL, V368, P60
[4]   Using instantaneous values for estimating fault locations on series compensated transmission lines [J].
Al-Dabbagh, M ;
Kapuduwage, SK .
ELECTRIC POWER SYSTEMS RESEARCH, 2005, 76 (1-3) :25-32
[5]  
Altman J., 2007, THESIS VIRGINIA POLY
[6]  
[Anonymous], 2007, P 2007 IEEE POW ENG, DOI DOI 10.1109/PES.2007.385545
[7]  
Bo W., 2009, Sustainable Power Generation and Supply, P1
[8]   New fault location scheme for a two-terminal transmission line using synchronized phasor measurements [J].
Brahma, S. M. .
2005/2006 IEEE/PES TRANSMISSION & DISTRIBUTION CONFERENCE & EXPOSITION, VOLS 1-3, 2006, :853-857
[9]   Fault location scheme for a multi-terminal transmission line using synchronized voltage measurements [J].
Brahma, SM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :1325-1331
[10]   Fault location on a transmission line using synchronized voltage measurements [J].
Brahma, SM ;
Girgis, AA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) :1619-1622