Research on Centralized Short-circuit and Leakage Protection for High-voltage System of Underground Central Substation

被引:0
作者
Gao Yan [1 ]
Ma Feng-lin [1 ]
Dong Guang-zhuai [2 ]
Xing Hai-long [2 ]
机构
[1] China Univ Min & Technol, Mech & Elect Informat Engn Inst, Beijing, Peoples R China
[2] Gu Shuyuan Coal Mine, Shanxi, Peoples R China
来源
CURRENT DEVELOPMENT OF MECHANICAL ENGINEERING AND ENERGY, PTS 1 AND 2 | 2014年 / 494-495卷
关键词
leakage protection; fault detection; pattern recognition;
D O I
10.4028/www.scientific.net/AMM.494-495.1753
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
According to the problems which are relay protection is difficult to adjust and when line fault occurs it will easily get override trip in the underground 6 kV power supply system in Gu Shu-yuan Coal Mine. This paper presents a centralized selective short circuit and leakage protection system. Which focuses on the analysis of the short circuit longitudinal differential protection, based on pattern recognition method of single-phase earth leakage protection principle, and completes the rapidity and selectivity of the leakage fault line selection. Through the simulation, experimental and field operation shows that the schemes can effectively improve the reliability and safety of high voltage power supply system in Gu Shu-yuan Coal Mine,it also establishes the necessary foundation of the goal of "network relay protection" in high voltage power supply system for in China.
引用
收藏
页码:1753 / +
页数:2
相关论文
共 7 条
[1]  
Ning Chuan-wen, 2005, NEW IDEAS POWER SUPP
[2]  
Shang Hai-zhu, 2005, TALKING SELECTIVITY
[3]  
Tang Yi, 1994, SELECTIVE LEAKAGE PR, p1 ~ 10
[4]  
Wang Chong-lin, 1997, POWER SUPPLY TECHNOL
[5]  
Wang Yan-wen, 2006, SELECTIVE LEAKAGE PR
[6]  
Wang Yan-wen, 1996, SECURITY TECHNOLOGIE
[7]  
Yu Jian-ming, 2001, POWER SUPPLY TECHNOL, P45