Reduction of waveform distortion in grid-injection current from single-phase utility interactive PV-inverter

被引:8
作者
Hamid, Muhammad Imran [1 ]
Jusoh, Awang [2 ]
机构
[1] Andalas Univ, Dept Elect Engn, Kecamatan Pauh, Sumatera Barat, Indonesia
[2] Univ Teknol Malaysia, Fac Elect Engn, Johor Baharu, Johor, Malaysia
关键词
PV-inverter; Distortion current; Conditioner; Utility factor; ACTIVE POWER FILTER; CONNECTED INVERTERS; PERFORMANCE; CONVERTER;
D O I
10.1016/j.enconman.2014.05.031
中图分类号
O414.1 [热力学];
学科分类号
摘要
As the natural behavior of energy source and design characteristic, the current generated by a grid-interactive PV-inverter may contain harmonics. This distortion component will be carried on from the PV-inverter during injection power into the grid. Excessive harmonics in a grid will lead to a variety of power quality problems. This paper presents a distortion reduction scheme, utilizing a fed forward single-phase, generation-side power conditioner with a structure that can be expanded for use in a three-phase system and can work independently under imbalanced condition. Conditioner is placed in parallel with the photovoltaic plant and it functions to compensate the plant's output current distortion, so that the total current flow to the grid is sinusoidal. This method also includes the implementation of a simpler control system for the conditioner, which consists of a combination of distortion current extraction, synchronization and a current control system, and realized through a TMS320F28335: a 150 MHz floating point DSP controller. Testing of the conditioner prototype, which was conducted on a real operation of a PV plant, showed that the scheme worked effectively within the overall operation range of the PV plant. This paper also discusses the potential of utility factor improvement of the PV-inverter and plant due to implementation of conditioner in the scheme. (c) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:212 / 226
页数:15
相关论文
共 30 条
[1]   Three-phase three-level grid interactive inverter with fuzzy logic based maximum power point tracking controller [J].
Altin, Necmi ;
Ozdemir, Saban .
ENERGY CONVERSION AND MANAGEMENT, 2013, 69 :17-26
[2]  
[Anonymous], WISP 2007
[3]  
[Anonymous], 1992, 5191992 IEEE
[4]   Application of multi-stage converter in distributed generation systems [J].
Banaei, M. R. ;
Salary, E. .
ENERGY CONVERSION AND MANAGEMENT, 2012, 62 :76-83
[5]   Power electronics as efficient interface in dispersed power generation systems [J].
Blaabjerg, F ;
Chen, Z ;
Kjaer, SB .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (05) :1184-1194
[6]   Variable Sampling Period Filter PLL for Distorted Three-Phase Systems [J].
Carugati, Ignacio ;
Maestri, Sebastian ;
Donato, Patricio G. ;
Carrica, Daniel ;
Benedetti, Mario .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2012, 27 (01) :321-330
[7]   PI State Space Current Control of Grid-Connected PWM Converters With LCL Filters [J].
Dannehl, Joerg ;
Fuchs, Friedrich Wilhelm ;
Thogersen, Paul Bach .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2010, 25 (09) :2320-2330
[8]   Performance of grid-tied PV facilities: A case study based on real data [J].
Diez-Mediavilla, M. ;
Dieste-Velasco, M. I. ;
Rodriguez-Amigo, M. C. ;
Garcia-Calderon, T. ;
Alonso-Tristan, C. .
ENERGY CONVERSION AND MANAGEMENT, 2013, 76 :893-898
[9]  
Farret FA, 2006, INTEGRATION OF ALTERNATIVE SOURCES OF ENERGY, P1
[10]  
Garrity T.F., 2009, Power Systems Conference, P1