New configurations of a heat recovery absorption heat pump integrated with a natural gas boiler for boiler efficiency improvement

被引:118
作者
Qu, Ming [1 ]
Abdelaziz, Omar [2 ]
Yin, Hongxi [3 ]
机构
[1] Purdue Univ, Sch Civil Engn, W Lafayette, IN 47906 USA
[2] Oak Ridge Natl Lab, Energy & Transportat Sci Div, Oak Ridge, TN 37831 USA
[3] Southeast Univ, Sch Architecture, Nanjing 210096, Jiangsu, Peoples R China
关键词
Natural gas boiler; Absorption heat pump; Heat recovery; Dew point; Flue gas; System configuration; PERFORMANCE; SYSTEM; STATE; LIBR;
D O I
10.1016/j.enconman.2014.06.083
中图分类号
O414.1 [热力学];
学科分类号
摘要
Conventional natural gas-fired boilers exhaust flue gas direct to the atmosphere at 150-200 degrees C, which, at such temperatures, contains large amount of energy and results in relatively low thermal efficiency ranging from 70% to 80%. Although condensing boilers for recovering the heat in the flue gas have been developed over the past 40 years, their present market share is still less than 25%. The major reason for this relatively slow acceptance is the limited improvement in the thermal efficiency of condensing boilers. In the condensing boiler, the temperature of the hot water return at the range of 50-60 degrees C, which is used to cool the flue gas, is very close to the dew point of the water vapor in the flue gas. Therefore, the latent heat, the majority of the waste heat in the flue gas, which is contained in the water vapor, cannot be recovered. This paper presents a new approach to improve boiler thermal efficiency by integrating absorption heat pumps with natural gas boilers for waste heat recovery (HRAHP). Three configurations of HRAHPs are introduced and discussed. The three configurations are modeled in detail to illustrate the significant thermal efficiency improvement they attain. Further, for conceptual proof and validation, an existing hot water-driven absorption chiller is operated as a heat pump at operating conditions similar to one of the devised configurations. An overall system performance and economic analysis are provided for decision-making and as evidence of the potential benefits. These three configurations of HRAHP provide a pathway to achieving realistic high-efficiency natural gas boilers for applications with process fluid return temperatures higher than or close to the dew point of the water vapor in the flue gas. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:175 / 184
页数:10
相关论文
共 27 条
[1]  
[Anonymous], 2011, US DEPARTMENT OF ENE
[2]  
[Anonymous], 1998, ENGINEERING EQUATION
[3]  
[Anonymous], 2004, BROAD AIR CONDITIONI
[4]  
ASME, 2008, POWER TEST CODES PTC
[5]   A model for analysis and design of H2O-LiBr absorption heat pumps [J].
Bakhtiari, Bahador ;
Fradette, Louis ;
Legros, Robert ;
Paris, Jean .
ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (02) :1439-1448
[6]  
Boeschen PL, 2000, ASHRAE TRANS, V106, P96
[7]  
Bureau of Labor Statistics, 2013, AVERAGE ENERGY PRICE
[8]   Evaluation of retrofitting a conventional natural gas fired boiler into a condensing boiler [J].
Che, DF ;
Liu, YH ;
Gao, CY .
ENERGY CONVERSION AND MANAGEMENT, 2004, 45 (20) :3251-3266
[9]   Condensing boiler applications in the process industry [J].
Chen, Qun ;
Finney, Karen ;
Li, Hanning ;
Zhang, Xiaohui ;
Zhou, Jue ;
Sharifi, Vida ;
Swithenbank, Jim .
APPLIED ENERGY, 2012, 89 (01) :30-36
[10]   Integration of absorption heat pumps in a Kraft pulp process for enhanced energy efficiency [J].
Costa, Andrea ;
Bakhtiari, Bahador ;
Schuster, Sebastian ;
Paris, Jean .
ENERGY, 2009, 34 (03) :254-260