An Investigation on Seismic Behavior of Three Interconnected Pieces of Substation Equipment

被引:35
作者
Mohammadi, R. Karami [1 ]
Tehrani, A. Pourkashani [1 ]
机构
[1] KN Toosi Univ Technol, Dept Civil Engn, Tehran 1996715433, Iran
关键词
Conductor slack; earthquake; failure probability; incremental dynamic analysis (IDA); interaction; EARTHQUAKE; CONDUCTORS;
D O I
10.1109/TPWRD.2013.2289365
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
High-voltage electrical substations are used to distribute power between residential, industrial, commercial, and agricultural regions. Previous earthquakes have shown that electrical substations are seismically vulnerable. Although equipment of these substations had been designed individually according to the electrical and seismic requirements, they have shown poor seismic performance resulting from interaction problems. In recent decades, some research has been done on the effects of interaction between substation equipment items, which are connected by flexible or rigid conductors. Although more than two items are usually connected to each other, only two items are assumed in most studies. In this paper, the effects of interaction between three interconnected items are investigated using incremental dynamic analyses. Two failure modes are considered, including failure of insulators and disconnection of conductors. The results are presented in terms of maximum sustainable ground motion acceleration and failure probability, and discussions are made to choose the best pair of interconnected items.
引用
收藏
页码:1613 / 1620
页数:8
相关论文
共 12 条
[1]   Testing and development of alternative flexible-bus geometries for interconnected substation equipment subjected to earthquakes [J].
Dastous, JB ;
Paquin, JY .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (03) :772-780
[2]   Experimental investigation on the dynamic behavior of flexible conductors between substation equipment during an earthquake [J].
Dastous, JB ;
Pierre, JR .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) :801-807
[3]  
Der Kiureghian A, 1999, INTERACTION INTERCON
[4]  
Der Kiureghian A, 2000, FURTHER STUDIES SEIS
[5]  
*FED EM MAN AG, 2005, FEMA440
[6]  
Filiatrault A., 2002, ELECT SUBSTATION EQU
[7]  
*IEEE, 2006, 15272006 IEEE
[8]  
Institute of Electrical and Electronics Engineers (IEEE), 2005, 6932005 IEEE
[9]  
Kiureghian AD, 2010, APPL GUIDE DESIGN FL
[10]   Estimation of Required Slack for Conductors Connecting Substation Equipment Subjected to Earthquake [J].
Mohammadi, R. Karami ;
Nikfar, Farzad ;
Akrami, Vahid .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (02) :709-717