Hilbert-Huang transform-based transient busbar protection algorithm

被引:31
作者
Guo, Zhenwei [1 ,2 ]
Yao, Jiangang [1 ]
Tan, Zhewen [3 ]
机构
[1] Hunan Univ, Coll Elect & Informat Engn, Changsha 410082, Hunan, Peoples R China
[2] Guilin Univ, Electromech Engn Coll, Guilin Univ Elect Technol, Guilin, Peoples R China
[3] Hunan Lishui River Basin Water Resources & Hydrop, Changsha, Hunan, Peoples R China
关键词
Hilbert transforms; busbars; power system protection; power system faults; power system reliability; fault diagnosis; Hilbert-Huang transform-based transient busbar protection algorithm; intrinsic mode function; IMF; fault detection; travelling wave; faulted line; reliability; fault travel wave-based algorithm; substation; ATP-Draw; voltage; 50; kV; TRANSMISSION-LINES; WAVELET-TRANSFORM; FAULT-LOCATION;
D O I
10.1049/iet-gtd.2014.0719
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A new algorithm for busbar protection is proposed based on the Hilbert-Huang transform in this study. The algorithm decomposes currents of all lines connecting to the busbar into intrinsic-mode functions and calculates the instantaneous amplitude of the first intrinsic mode function (IMF). Then, the instantaneous amplitude is normalised to eliminate the impact of fault initial angle and transition resistance. When a fault occurs on the busbar, the initial travelling waves on head ends of the lines all have great instantaneous amplitudes; when a fault occurs on any line, the travelling wave on the faulted line is of great instantaneous amplitude, whereas the initial travelling waves on healthy lines are of small instantaneous amplitudes. Thus, through analysing the detected instantaneous amplitudes of travelling waves, a new busbar protection scheme can be constructed, which achieves a high reliability relative to other fault-travel-wave-based algorithms. According to simulation results on a 500 kV substation modelled in ATP-Draw, the graphical preprocessor to ATP-EMTP windows version, the proposed algorithm is effective in determining various types of faults.
引用
收藏
页码:2032 / 2039
页数:8
相关论文
共 14 条
[1]   Fault location in power networks with mixed feeders using the complex space-phasor and Hilbert-Huang transform [J].
Bernadic, Alen ;
Leonowicz, Zbigniew .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 42 (01) :208-219
[2]   A new non-communication protection technique for transmission lines [J].
Bo, ZQ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (04) :1073-1078
[3]   A new digital busbar protection technique based on frequency information during CT saturation [J].
Eissa, M. M. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 45 (01) :42-49
[4]   A transient current based busbar protection scheme using Wavelet Transforms [J].
Gafoor, Shaik Abdul ;
Rao, Pulipaka V. Ramana .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2011, 33 (04) :1049-1053
[5]   A new method for non-unit protection of power transmission lines based on fault resistance and fault angle reduction [J].
Guo, Zhenwei ;
Yao, Jiangang ;
Yang, Shengjie ;
Zhang, Hong ;
Mao, Tian ;
Thanh Long Duong .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 55 :760-769
[6]   Speech pitch determination based on Hilbert-Huang transform [J].
Huang, H ;
Pan, JQ .
SIGNAL PROCESSING, 2006, 86 (04) :792-803
[7]  
Jiandong D., 2004, P CSEE, V6, P7
[8]   High-speed differential busbar protection using wavelet-packet transform [J].
Mohammed, ME .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2005, 152 (06) :927-933
[9]   A comparison study of improved Hilbert-Huang transform and wavelet transform: Application to fault diagnosis for rolling bearing [J].
Peng, ZK ;
Tse, PW ;
Chu, FL .
MECHANICAL SYSTEMS AND SIGNAL PROCESSING, 2005, 19 (05) :974-988
[10]   Computationally efficient wavelet-transform-based digital directional protection for busbars [J].
Valsan, Simi P. ;
Swarup, K. S. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (03) :1342-1350