A New Multi-Conductor Transmission Line Model of Transformer Winding for Frequency Response Analysis Considering the Frequency-Dependent Property of the Lamination Core

被引:12
作者
Wang, Song [1 ,2 ]
Guo, Ze [1 ,2 ]
Zhu, Ting [1 ,2 ]
Feng, Hanke [1 ,2 ]
Wang, Shuhong [1 ,2 ]
机构
[1] Xi An Jiao Tong Univ, Fac Elect Engn, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Shaanxi, Peoples R China
[2] Shaanxi Key Lab Smart Grid, Xian 710049, Shaanxi, Peoples R China
关键词
transformer; multi-conductor transmission line model (MTL); frequency response analysis (FRA); frequency-dependent property; POWER TRANSFORMERS; AXIAL DISPLACEMENT; RADIAL DEFORMATION; FRA DIAGNOSTICS;
D O I
10.3390/en11040826
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Multi-conductor transmission line (MTL) model of power transformer winding for frequency response analysis (FRA) has been successfully applied for the purpose of studying the characteristics of winding deformations. Most of the time it is considered that, at a frequency above 10 kHz, the flux does not penetrate the core, and the iron core losses due to hysteresis and eddy current can be neglected accordingly. However, In fact, there is still a little flux residing In the core, and it has a significant influence on inductances and resistances of transformer winding even up to approximately 1 MHz. In this paper, by introducing the anisotropic complex permeability of the lamination core into calculating inductances and resistances of the MTL model, a new MTL model considering the frequency-dependent property of the lamination core for FRA is presented. In addition, the accuracy and effectiveness of the MTL model are validated by means of a comparison between measured and emulated FRA results In a wide frequency range from 10 Hz up to 10 MHz. This precise MTL model of the transformer winding provides us a more objective and positive condition for simulation research of winding deformation detection.
引用
收藏
页数:12
相关论文
共 25 条
[1]   Exploring possibilities for characterization of power transformer insulation by frequency response analysis (FRA) [J].
Abeywickrama, KGNB ;
Serdyuk, YV ;
Gubanski, SM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1375-1382
[2]  
Abeywickrama N., 2007, IEEE T MAGN, V23, P4076
[3]   High-frequency modeling of power transformers for use in frequency response analysis (FRA) [J].
Abeywickrama, Nilanga ;
Serdyuk, Yuriy V. ;
Gubanski, Stanislaw M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) :2042-2049
[4]   Understanding Power Transformer Frequency Response Analysis Signatures [J].
Abu-Siada, A. ;
Hashemnia, N. ;
Islam, S. ;
Masoum, Mohammad A. S. .
IEEE ELECTRICAL INSULATION MAGAZINE, 2013, 29 (03) :48-56
[5]   A Review of Frequency Response Analysis Methods for Power Transformer Diagnostics [J].
Alsuhaibani, Saleh ;
Khan, Yasin ;
Beroual, Abderrahmane ;
Malik, Nazar Hussain .
ENERGIES, 2016, 9 (11)
[6]  
Cigre W. G., 2008, 342 CIGRE
[7]   TRANSFORMER DIAGNOSTIC TESTING BY FREQUENCY-RESPONSE ANALYSIS [J].
DICK, EP ;
ERVEN, CC .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (06) :2144-2153
[8]   Analysis of Physical Transformer Circuits for Frequency Response Interpretation and Mechanical Failure Diagnosis [J].
Dinh Anh Khoi Pham ;
Gockenbach, Ernst .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (03) :1491-1499
[9]   Current Status and Future Trends in Frequency-Response Analysis With a Transformer in Service [J].
Gomez-Luna, Eduardo ;
Aponte Mayor, Guillermo ;
Gonzalez-Garcia, Carlos ;
Pleite Guerra, Jorge .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (02) :1024-1031
[10]   Improved Power Transformer Winding Fault Detection using FRA Diagnostics - Part 1: Axial Displacement Simulation [J].
Hashemnia, Naser ;
Abu-Siada, A. ;
Islam, S. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (01) :556-563