Using Fall-of-Potential Measurements to Improve Deep Soil Resistivity Estimates

被引:25
作者
Southey, Robert D. [1 ]
Siahrang, Majid [1 ]
Fortin, Simon [1 ]
Dawalibi, Farid P. [1 ]
机构
[1] Safe Engn Serv & Technol Ltd, Laval, PQ H7L 6E8, Canada
关键词
Fall-of-potential (FOP) test; ground impedance measurement; power system grounding; soil resistivity data interpretation; soil resistivity measurement; touch voltage; GROUNDING SYSTEMS;
D O I
10.1109/TIA.2015.2428679
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
When measuring the ground impedance of an electrically isolated grounding system, it sometimes happens that the test electrodes are placed at considerably greater distances from the installation under test than the maximum electrode spacing used during the soil resistivity measurements carried out during the predesign phase of the grounding system. As a result, ground impedance measurements carried out with the fall-of-potential method may contain valuable supplemental information about deep soil strata that can improve grounding system performance predictions made during the design phase with computer modeling software and explain discrepancies encountered between predicted and measured ground impedance values. These data can be also used during subsequent grounding design work associated with facility expansion. It is shown in this paper how, in the absence of interfering metallic infrastructure, such ground impedance measurements can be converted into apparent soil resistivity values corresponding to deeper soil layers, with an example showing how dramatic improvements in grounding system performance predictions can be obtained.
引用
收藏
页码:5023 / 5029
页数:7
相关论文
共 9 条
[1]  
[Anonymous], 2000, IEEE Std 80-2000
[2]   MEASUREMENTS AND COMPUTATIONS OF THE PERFORMANCE OF GROUNDING SYSTEMS BURIED IN MULTILAYER SOILS [J].
DAWALIBI, F ;
BARBEITO, N .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (04) :1483-1489
[3]   EARTH RESISTIVITY MEASUREMENT INTERPRETATION TECHNIQUES [J].
DAWALIBI, F ;
BLATTNER, CJ .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (02) :374-382
[4]   Integrated analysis software for grounding, EMF, and EMI [J].
Dawalibi, Farid P. ;
Donoso, Fernando .
IEEE Computer Applications in Power, 1993, 6 (02) :19-24
[5]   BEHAVIOR OF GROUNDING SYSTEMS IN MULTILAYER SOILS - A PARAMETRIC ANALYSIS [J].
DAWALIBI, FP ;
MA, J ;
SOUTHEY, RD .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (01) :334-341
[6]  
He J., 2012, METHODOLOGY TECHNOLO, P86
[7]  
IEEE Guide for Measuring Earth Resistivity, 812012 IEEE
[8]   Efficient ground grid designs in layered soils [J].
Lee, HS ;
Kim, JH ;
Dawalibi, FP ;
Ma, JX .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (03) :745-751
[9]  
Southey RD, 2002, POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS, P98, DOI 10.1109/ICPST.2002.1053512