Enhancing Network Parameter Error Detection and Correction via Multiple Measurement Scans

被引:30
作者
Lin, Yuzhang [1 ]
Abur, Ali [1 ]
机构
[1] Northeastern Univ, Dept Elect & Comp Engn, Boston, MA 02115 USA
基金
美国国家科学基金会;
关键词
Lagrange multiplier; multiple measurement scans; parameter error; state estimation; TAP POSITION ESTIMATION; STATE ESTIMATION; IDENTIFICATION;
D O I
10.1109/TPWRS.2016.2608964
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Although the normalized Lagrange multiplier (NLM) method has been shown to be very effective for network parameter error identification, errors in parameters corresponding to insensitive NLMs still remain difficult to detect and correct. This paper proposes an enhanced method for detecting and correcting network parameter errors based on multiple measurement scans. The method is developed by first deriving the relationship between parameter errors and the associated Langrage multipliers in state estimation. This is then used to clarify the reason behind the sensitivity issue of NLMs and the improvements made by performing multiple scans. An approach for estimating the necessary number of scans for satisfying various detection requirements is also proposed. Moreover, a local parameter error correction procedure based on multiple scans is presented, with detailed discussion of the local network selection and the number of required measurement scans. Simulation results in a very large utility system in North America illustrate the effectiveness of the analysis and methods proposed in this paper.
引用
收藏
页码:2417 / 2425
页数:9
相关论文
共 19 条
[1]  
Abur A., 2004, POWER SYSTEM STATE E
[2]  
Allam M., 1974, IEEK PES 1974 SUMMER, P331
[3]   Generalized state estimation [J].
Alsac, O ;
Vempati, N ;
Stott, B ;
Monticelli, A .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1998, 13 (03) :1069-1075
[4]  
Clements K., 1974, P IEEE PES SUMM POW, P311
[5]   TRANSFORMER TAP POSITION ESTIMATION [J].
FLETCHER, DL ;
STADLIN, WO .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (11) :3680-3686
[6]  
HANDSCHIN E, 1995, IEEE T POWER SYST, V10, P810, DOI 10.1109/59.387921
[7]  
Lin Y., 2015, P N AM POW S CHARL N
[8]   PARAMETER ERROR IDENTIFICATION AND ESTIMATION IN POWER-SYSTEM STATE ESTIMATION [J].
LIU, WHE ;
LIM, SL .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (01) :200-209
[9]   ESTIMATION OF PARAMETER ERRORS FROM MEASUREMENT RESIDUALS IN STATE ESTIMATION [J].
LIU, WHE ;
VANCUTSEM, T ;
DEBS, AS ;
WU, FF ;
LUN, SM .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) :81-89
[10]   TRANSFORMER TAP POSITION ESTIMATION - FIELD EXPERIENCE [J].
MUKHERJEE, BK ;
HANSON, SO ;
FUERST, GR ;
MONROE, CA .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1984, 103 (06) :1454-1458