Leak-Before-Break Main Failure Prevention for Water Distribution Pipes Using Acoustic Smart Water Technologies: Case Study in Adelaide

被引:45
作者
Stephens, Mark [1 ]
Gong, Jinzhe [2 ]
Zhang, Chi [3 ]
Marchi, Angela [1 ]
Dix, Luke [1 ]
Lambert, Martin F. [3 ]
机构
[1] South Australian Water Corp, 250 Victoria Sq, Adelaide, SA 5000, Australia
[2] Deakin Univ, Sch Engn, Geelong Waurn Ponds Campus, Geelong, Vic 3216, Australia
[3] Univ Adelaide, Sch Civil Environm & Min Engn, Adelaide, SA 5005, Australia
基金
澳大利亚研究理事会;
关键词
Accelerometer; Acoustic; Leak-before-break; Pipe burst; Smart water network; BURSTS;
D O I
10.1061/(ASCE)WR.1943-5452.0001266
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Water main breaks in city areas can cause significant economic loss, interrupt traffic, and result in negative publicity for utilities. The South Australian Water Corporation (SA Water) has taken a proactive approach to reduce water main breaks in the Adelaide, Australia, central business district (CBD) by detecting developing pipe cracks/leaks using distributed acoustic sensors (accelerometers) with customized analytics and internet of things (IoT) technologies. This paper reports the findings and the outcomes of this initiative 24 months after the first commissioning of the continuous leak detection system. The acoustic data analytics team (comprising the authors) has successfully interpreted acoustic data from numerous cracked pipes in the Adelaide CBD, with approximately 55% of all developing leaks associated with cracked pipes being able to be detected before uncontrolled failure (i.e., before unplanned interruption of customers and/or third party economic damage). Furthermore, the localization and repair of specific cracks (sometimes through sections of corroded cast iron pipe walls) can help justify extending the service life of the water main as points of weakness (faults) are specifically rectified. However, only 45% of the developing cracks have been able to be repaired, after detection, under controlled conditions (i.e., before the planned interruption of customers) due to practical limitations affecting operational responses. The results have confirmed the additional insight that can be obtained by continuously collecting acoustic data in terms of distinguishing environmental and crack noises as well as circumferential from longitudinal cracks.
引用
收藏
页数:13
相关论文
共 21 条
  • [1] Evaluation of water losses in distribution networks
    ArreguinCortes, FI
    OchoaAlejo, LH
    [J]. JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT-ASCE, 1997, 123 (05): : 284 - 291
  • [2] Leak-before-break: Global perspectives and procedures
    Bourga, R.
    Moore, P.
    Janin, Y. -J.
    Wang, B.
    Sharples, J.
    [J]. INTERNATIONAL JOURNAL OF PRESSURE VESSELS AND PIPING, 2015, 129 : 43 - 49
  • [3] Leakage Detection Using Smart Water System: Combination of Water Balance and Automated Minimum Night Flow
    Farah, Elias
    Shahrour, Isam
    [J]. WATER RESOURCES MANAGEMENT, 2017, 31 (15) : 4821 - 4833
  • [4] Development and Field Validation of a Burst Localization Methodology
    Farley, B.
    Mounce, S. R.
    Boxall, J. B.
    [J]. JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT, 2013, 139 (06) : 604 - 613
  • [5] Jiang R, 2017, WATER PRACT TECHNOL, V12, P487, DOI 10.2166/wpt.2017.058
  • [6] Novel Approach to Detecting Pipe Bursts in Water Distribution Networks
    Kang, Doosun
    Lansey, Kevin
    [J]. JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT, 2014, 140 (01) : 121 - 127
  • [7] Kodikara J, 2017, PIPELINES 2017: CONDITION ASSESSMENT, SURVEYING, AND GEOMATICS, P561
  • [8] Online Burst Detection and Location of Water Distribution Systems and Its Practical Applications
    Lee, Shin Je
    Lee, Gibaek
    Suh, Jung Chul
    Lee, Jong Min
    [J]. JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT, 2016, 142 (01)
  • [9] Pipeline break detection using pressure transient monitoring
    Misiunas, D
    Vítkovsky, J
    Olsson, G
    Simpson, A
    Lambert, M
    [J]. JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT, 2005, 131 (04) : 316 - 325
  • [10] New Laboratory Test Facility Developed to Investigate the Leak-Before-Break Window of Large-Diameter Cast Iron Water Pipes
    Rathnayaka, Suranji
    Shannon, Benjamin
    Jiang, Rui
    Kodikara, Jayantha
    [J]. JOURNAL OF PIPELINE SYSTEMS ENGINEERING AND PRACTICE, 2018, 9 (03)