摘要
High-voltage cables with paper-oil based insulation are still widely used in electric power Systems. One issue with EMTP-type modeling and simulation of such cables is that the permittivity of the insulation is frequency-dependent, thereby contributing to the dispersion of traveling waves. This frequency dependency is not taken into account in currently available EMTP-type programs. This paper presents field measurements from step voltage excitations on three different oil-filled cables with steel armoring. The waveforms are compared to EMTP-type simulations, demonstrating significant deviations from the measured waveforms. The frequency-dependency of the permittivity is next taken into account using a formula obtained by Breien and Johansen, and the modeling and simulation procedure is repeated. Inclusion of the frequency-dependency is shown to bring the simulation results much closer to the measured waveforms. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:43 / 49
页数:7
相关论文
共 7 条
[1]  
[Anonymous], 2014, A2C439 JWG 1, V577A
[2]  
[Anonymous], 1986, EMTP Theory Book
[3]   ATTENUATION OF TRAVELLING WAVES IN SINGLE-PHASE HIGH-VOLTAGE CABLES [J].
BREIEN, O ;
JOHANSEN, I .
PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1971, 118 (06) :787-&
[4]   Study of Transformer Resonant Overvoltages Caused by Cable-Transformer High-Frequency Interaction [J].
Gustavsen, Bjorn .
IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (02) :770-779
[6]   A universal model for accurate calculation of electromagnetic transients on overhead lines and underground cables [J].
Morched, A ;
Gustavsen, B ;
Tartibi, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1999, 14 (03) :1032-1038
[7]  
Wedepohl L.M., 1973, P I ELECTR ENG, V120, P252