Simplified model for thermal comfort, IAQ and energy savings in rooms conditioned by displacement ventilation aided with transient personalized ventilation

被引:35
|
作者
Al Assaad, Douaa [1 ]
Habchi, Carine [2 ]
Ghali, Kamel [1 ]
Ghaddar, Nesreen [1 ]
机构
[1] Amer Univ Beirut, Mech Engn Dept, POB 11-0236, Beirut 11072020, Lebanon
[2] Lebanese Univ, Fac Engn, Dept Mech Engn, Branch 2, Roumieh, Lebanon
关键词
Displacement ventilation; Personalized ventilation; Intermittent jet; Thermal comfort; Indoor air quality; energy savings; MOMENTUM RESPIRATORY ACTIVITIES; CROSS-CONTAMINATION; AIR-QUALITY; DESK FANS; PERFORMANCE; OFFICE; EXPOSURE; SYSTEM; FLOW; CONJUNCTION;
D O I
10.1016/j.enconman.2018.02.033
中图分类号
O414.1 [热力学];
学科分类号
摘要
The aim of this work is to evaluate the performance of an intermittent personalized ventilation (PV) system assisting a displacement ventilation (DV) system based on its ability in improving thermal comfort and protecting occupants from floor emitted passive contaminants. A simplified transient mathematical model was developed of heat and species transport to predict the temperature and concentration fields in the macroclimate room air, in the thermal plume induced by the occupant and internal heat sources and within the intermittent PV jet facing the occupant face at a fixed distance. The model's predictions of temperature and concentration were experimentally validated for a PV frequency range [0.3-1 Hz] in a climatic chamber conditioned with a DV system assisted with an intermittent PV jet. Good agreement was found between the predicted and measured values of temperature and concentration of tracer gas in the different regions of macroclimate air, thermal plume, and PV jet. The validated model was used to conduct a case study where comfort and air quality were assessed and the energy consumption of the transient PV + DV system was compared to steady PV + DV and standalone DV systems. It was found that the intermittent PV range [0.3-1 Hz] was able to improve comfort compared to steady PV and provide acceptable air quality. Moreover, energy analysis showed that the intermittent PV + DV (40 L/s) was able to achieve maximum energy savings of 54.61% and 31.58% compared to a standalone DV and steady PV respectively for equivalent comfort.
引用
收藏
页码:203 / 217
页数:15
相关论文
共 25 条
  • [21] Energy savings and guaranteed thermal comfort in hotel rooms through nonlinear model predictive controllers
    Acosta, Adriana
    Gonzalez, Ana I.
    Zamarreno, Jesus M.
    Alvarez, Victor
    ENERGY AND BUILDINGS, 2016, 129 : 59 - 68
  • [22] Energy savings of commercial kitchen ventilation and air conditioning systems based on cooking oil control and thermal comfort
    Zhang, Chengquan
    Yang, Fan
    Liu, Huan
    Xia, Yunfei
    He, Lianjie
    Yu, Yanlei
    Zeng, Lingjie
    Cao, Changsheng
    Gao, Jun
    ENERGY AND BUILDINGS, 2024, 315
  • [23] A novel occupant-centric stratum ventilation system using computer vision: Occupant detection, thermal comfort, air quality, and energy savings
    Yang, Bin
    Liu, Yihang
    Liu, Pengju
    Wang, Faming
    Cheng, Xiaogang
    Lv, Zhihan
    BUILDING AND ENVIRONMENT, 2023, 237
  • [24] Balancing thermal comfort and energy conservation- A multi-objective optimization model for controlling air-condition and mechanical ventilation systems
    Lin, Chiuhsiang Joe
    Wang, Kung-Jeng
    Dagne, Teshome Bekele
    Woldegiorgis, Bereket Haile
    BUILDING AND ENVIRONMENT, 2022, 219
  • [25] New airborne pathogen transport model for upper-room UVGI spaces conditioned by chilled ceiling and mixed displacement ventilation: Enhancing air quality and energy performance
    Kanaan, Mohamad
    Ghaddar, Nesreen
    Ghali, Kamel
    Araj, Georges
    ENERGY CONVERSION AND MANAGEMENT, 2014, 85 : 50 - 61