Simplified model for thermal comfort, IAQ and energy savings in rooms conditioned by displacement ventilation aided with transient personalized ventilation

被引:35
作者
Al Assaad, Douaa [1 ]
Habchi, Carine [2 ]
Ghali, Kamel [1 ]
Ghaddar, Nesreen [1 ]
机构
[1] Amer Univ Beirut, Mech Engn Dept, POB 11-0236, Beirut 11072020, Lebanon
[2] Lebanese Univ, Fac Engn, Dept Mech Engn, Branch 2, Roumieh, Lebanon
关键词
Displacement ventilation; Personalized ventilation; Intermittent jet; Thermal comfort; Indoor air quality; energy savings; MOMENTUM RESPIRATORY ACTIVITIES; CROSS-CONTAMINATION; AIR-QUALITY; DESK FANS; PERFORMANCE; OFFICE; EXPOSURE; SYSTEM; FLOW; CONJUNCTION;
D O I
10.1016/j.enconman.2018.02.033
中图分类号
O414.1 [热力学];
学科分类号
摘要
The aim of this work is to evaluate the performance of an intermittent personalized ventilation (PV) system assisting a displacement ventilation (DV) system based on its ability in improving thermal comfort and protecting occupants from floor emitted passive contaminants. A simplified transient mathematical model was developed of heat and species transport to predict the temperature and concentration fields in the macroclimate room air, in the thermal plume induced by the occupant and internal heat sources and within the intermittent PV jet facing the occupant face at a fixed distance. The model's predictions of temperature and concentration were experimentally validated for a PV frequency range [0.3-1 Hz] in a climatic chamber conditioned with a DV system assisted with an intermittent PV jet. Good agreement was found between the predicted and measured values of temperature and concentration of tracer gas in the different regions of macroclimate air, thermal plume, and PV jet. The validated model was used to conduct a case study where comfort and air quality were assessed and the energy consumption of the transient PV + DV system was compared to steady PV + DV and standalone DV systems. It was found that the intermittent PV range [0.3-1 Hz] was able to improve comfort compared to steady PV and provide acceptable air quality. Moreover, energy analysis showed that the intermittent PV + DV (40 L/s) was able to achieve maximum energy savings of 54.61% and 31.58% compared to a standalone DV and steady PV respectively for equivalent comfort.
引用
收藏
页码:203 / 217
页数:15
相关论文
共 44 条
[1]   Optimized performance of displacement ventilation aided with chair fans for comfort and indoor air quality [J].
Abou Hweij, Walid ;
Ghaddar, Nesreen ;
Ghali, Kamel ;
Habchi, Carine .
ENERGY AND BUILDINGS, 2016, 127 :907-919
[2]   A numerical study on the effects of exhaust locations on energy consumption and thermal environment in an office room served by displacement ventilation [J].
Ahmed, Ahmed Qasim ;
Gao, Shian ;
Kareem, Ali Khaleel .
ENERGY CONVERSION AND MANAGEMENT, 2016, 117 :74-85
[3]   Effectiveness of intermittent personalized ventilation in protecting occupant from indoor particles [J].
Al Assaad, Douaa ;
Habchi, Carine ;
Ghali, Kamel ;
Ghaddar, Nesreen .
BUILDING AND ENVIRONMENT, 2018, 128 :22-32
[4]   Mixing ventilation coupled with personalized sinusoidal ventilation: Optimal frequency and flow rate for acceptable air quality [J].
Al Assaad, Douaa ;
Ghali, Kamel ;
Ghaddar, Nesreen ;
Habchi, Carine .
ENERGY AND BUILDINGS, 2017, 154 :569-580
[5]   A multi-segmented human bioheat model for transient and asymmetric radiative environments [J].
Al-Othmani, M. ;
Ghaddar, N. ;
Ghali, K. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2008, 51 (23-24) :5522-5533
[6]   A simplified combined displacement and personalized ventilation model [J].
Alain, Makhoul ;
Kamel, Ghali ;
Nesreen, Ghaddar .
HVAC&R RESEARCH, 2012, 18 (04) :737-749
[7]  
American Society of Mechanical Engineers, ASME AG 1A 2004 ADD
[8]  
ASHRAE, 2010, ANSI/ASHRAE Standard 55-2020
[9]   Dispersal of exhaled air and personal exposure in displacement ventilated rooms [J].
Bjorn, E ;
Nielsen, PV .
INDOOR AIR, 2002, 12 (03) :147-164
[10]   Performance of personalized ventilation in conjunction with mixing and displacement ventilation [J].
Cermak, R ;
Melikov, AK ;
Forejt, L ;
Kovar, O .
HVAC&R RESEARCH, 2006, 12 (02) :295-311