Experimental evaluation of the inter-stage conditions of a two-stage refrigeration cycle using a compound compressor

被引:46
作者
Torrella, E. [2 ]
Llopis, R. [1 ]
Cabello, R. [1 ]
机构
[1] Jaume 1 Univ, Dept Mech Engn & Construct, E-12071 Castellon de La Plana, Spain
[2] Univ Politecn Valencia, Dept Appl Thermodynam, E-46022 Valencia, Spain
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2009年 / 32卷 / 02期
关键词
Refrigerated system; Two-stage system; Compression system; R404A; Experiment; Performance;
D O I
10.1016/j.ijrefrig.2008.05.006
中图分类号
O414.1 [热力学];
学科分类号
摘要
The aim of the present paper is to detail an analysis, based on experimental data, of the inter-stage working conditions of a two-stage vapour compression facility equipped with a compound compressor, which operates with the most usual inter-stage configurations (two-stage with direct liquid injection and two-stage with subcooler) in medium- and low-capacity commercial refrigeration applications. The experimental analysis is performed in an evaporating temperature range between -36 and -20 degrees C, and in a condensing temperature range between 30 and 47 degrees C, using one of the fluids most widely-used in Europe for low-temperature applications, the R-404a. The inter-stage working temperature/pressure obtained in the tests has been contrasted with the two usual criterion of the optimum working conditions definition: the arithmetical mean of the refrigerant condensing and evaporating temperatures and the criterion of equal pressure ratios in both stages. This paper presents the differences and affinities with the criterion and analyses the influence of the intermediate systems (direct liquid injection and subcooler) on the inter-stage operating conditions. (C) 2008 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:307 / 315
页数:9
相关论文
共 13 条
[1]  
[Anonymous], 1955, P 9 INT C REFR
[2]  
[Anonymous], P 13 INT C REFR
[3]  
[Anonymous], HVAC RES
[4]  
[Anonymous], 1959, ALLGEMEINE WARMETECH
[5]  
[Anonymous], INT J EXERGY
[6]  
Baumann K., 1961, Kaltetechnik, V13, P210
[7]  
De Lepeleire G., 1973, 13 INT C REFR WASH, P39
[8]   Design and rating of a two-stage vapor-compression refrigeration system [J].
Khan, JUR ;
Zubair, SM .
ENERGY, 1998, 23 (10) :867-878
[9]   Thermodynamic optimization of finite time vapor compression refrigeration systems [J].
Khan, JUR ;
Zubair, SM .
ENERGY CONVERSION AND MANAGEMENT, 2001, 42 (12) :1457-1475
[10]   A dynamic mathematical model of a shell-and-tube evaporator. Validation with pure and blend refrigerants [J].
Llopis, R. ;
Cabello, R. ;
Navarro-Esbri, J. ;
Torrella, E. .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2007, 31 (03) :232-244