Implications of biological activated carbon filters for micropollutant removal in wastewater treatment

被引:53
作者
Fundneider, T. [1 ]
Alonso, V. Acevedo [1 ]
Wick, A. [2 ]
Albrecht, D. [2 ]
Lackner, S. [1 ]
机构
[1] Tech Univ Darmstadt, Inst IWAR, Chair Wastewater Engn, Franziska Braun Str 7, D-64287 Darmstadt, Germany
[2] Fed Inst Hydrol BfG, Mainzer Tor 1, D-56068 Koblenz, Germany
关键词
Activated carbon filtration; Adsorption; Biodegradation; Empty bed contact time (EBCT); Micropollutants; Tertiary treatment; ORGANIC MICRO-POLLUTANTS; DRINKING-WATER; ADSORPTION; FILTRATION; BIODEGRADATION; PERFORMANCE; PHARMACEUTICALS; COMBINATION; MATTER; SIZE;
D O I
10.1016/j.watres.2020.116588
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Granulated Activated Carbon (GAC) filtration is a common process for advanced wastewater treatment. In such filters, the removal of organic substances results from adsorptive as well as biological processes. This work investigated the potential of biological processes and their influence on GAC-filter performance. During 32 months, the removal of micropollutants,Dissolved Organic Carbon (DOC) and the spectral absorption coefficient was monitored in six GAC-filters. The effects of pre-treatment (cloth- and/or membrane-filtration), EBCT (from 6 - 35 min) and GAC-type were evaluated. Likewise, the impact of the influent's fluctuations in temperature, flow and concentration (ammonia, nitrate, and soluble reactive phosphorus (sRP)) were analysed. Biological processes were tracked by the frequency of backwashing, oxygen consumption, removal of poorly absorbable micropollutants and production of transformation products. Pre-treatment influenced biofilm growth significantly. Membrane filtration delayed the first backwashing event by 122 d in comparison to cloth-filtration, where the first backwash was conducted after only 21 d. Removal of poorly absorbable substances was observed early on (40 - 50 d). Parallel operation contributed to a better utilisation of the GAC-capacity and the biological removal potential. Influent nitrogen species > 0.5 mg N/L promoted biofilm growth, whereas sRP seemed to have no effect. The developed biofilm and optimal operating conditions led to longer life spans of the GAC-filters, making carbon usage rates comparable to those from PAC applications. The results suggest that biological processes accounted for about 25 - 42% of the totally removed DOC at the end of the operation. (C) 2020 Elsevier Ltd. All rights reserved.
引用
收藏
页数:11
相关论文
共 48 条
[1]   Combination of granular activated carbon adsorption and deep-bed filtration as a single advanced wastewater treatment step for organic micropollutant and phosphorus removal [J].
Altmann, Johannes ;
Rehfeld, Daniel ;
Traeder, Kai ;
Sperlich, Alexander ;
Jekel, Martin .
WATER RESEARCH, 2016, 92 :131-139
[2]  
Benstom F., 2017, GRANULIERTE AKTIVKOH
[3]   Removal of micropollutants in municipal wastewater treatment plants by powder-activated carbon [J].
Boehler, M. ;
Zwickenpflug, B. ;
Hollender, J. ;
Ternes, T. ;
Joss, A. ;
Siegrist, H. .
WATER SCIENCE AND TECHNOLOGY, 2012, 66 (10) :2115-2121
[4]  
Cecen F, 2012, ACTIVATED CARBON FOR WATER AND WASTEWATER TREATMENT: INTEGRATION OF ADSORPTION AND BIOLOGICAL TREATMENT, P1
[5]  
DIN-EN-ISO, 2004, BEST PHOSPH PHOT VER
[6]  
DVGW, 2011, ENTF ORG STOFF BEI T
[7]  
Flemming H.-C., 1991, GAS WASSER FACH WASS, P197
[8]   Tertiary phosphorus removal to extremely low levels by coagulation-flocculation and cloth-filtration [J].
Fundneider, T. ;
Alejo, L. ;
Lackner, S. .
WATER SCIENCE AND TECHNOLOGY, 2020, 82 (01) :131-143
[9]  
Fundneider T., 2020, FILTRATION AKTIVKOHL, DOI 10.25534/tuprints-00012020
[10]   Oxypurinol - A novel marker for wastewater contamination of the aquatic environment [J].
Funke, Jan ;
Prasse, Carsten ;
Eversloh, Christian Luetke ;
Ternes, Thomas A. .
WATER RESEARCH, 2015, 74 :257-265