On the Acoustic Filtering of the Pipe and Sensor in a Buried Plastic Water Pipe and its Effect on Leak Detection: An Experimental Investigation

被引:80
作者
Almeida, Fabricio [1 ]
Brennan, Michael [1 ]
Joseph, Phillip [2 ]
Whitfield, Stuart [3 ]
Dray, Simon [4 ]
Paschoalini, Amarildo [1 ]
机构
[1] UNESP FEIS, Dept Mech Engn, BR-15385000 Ilha Solteira, Brazil
[2] ISVR, Southampton SO17 1BJ, Hants, England
[3] South Staffs Water Plc, Walsall WS2 7PD, W Midlands, England
[4] Hydrosave Ltd, Swallow Court, Kettering NN15 6XX, England
关键词
leak detection; plastic water distribution pipes; acoustic methods; AXISYMMETRICAL WAVE-PROPAGATION; TIME-DELAY ESTIMATION; FLUID-FILLED PIPES; NOISE;
D O I
10.3390/s140305595
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Acoustic techniques have been used for many years to find and locate leaks in buried water distribution systems. Hydrophones and accelerometers are typically used as sensors. Although geophones could be used as well, they are not generally used for leak detection. A simple acoustic model of the pipe and the sensors has been proposed previously by some of the authors of this paper, and their model was used to explain some of the features observed in measurements. However, simultaneous measurements of a leak using all three sensor-types in controlled conditions for plastic pipes has not been reported to-date and hence they have not yet been compared directly. This paper fills that gap in knowledge. A set of measurements was made on a bespoke buried plastic water distribution pipe test rig to validate the previously reported analytical model. There is qualitative agreement between the experimental results and the model predictions in terms of the differing filtering properties of the pipe-sensor systems. A quality measure for the data is also presented, which is the ratio of the bandwidth over which the analysis is carried out divided by the centre frequency of this bandwidth. Based on this metric, the accelerometer was found to be the best sensor to use for the test rig described in this paper. However, for a system in which the distance between the sensors is large or the attenuation factor of the system is high, then it would be advantageous to use hydrophones, even though they are invasive sensors.
引用
收藏
页码:5595 / 5610
页数:16
相关论文
共 18 条
[1]  
Almeida F.C.L., 2013, Ph.D. thesis
[2]  
[Anonymous], AWA WATER J ASSET MA
[3]  
[Anonymous], 1971, Random Data: Analysis and Measurement Procedures
[4]   Computational fluid dynamic simulation of small leaks in water pipelines for direct leak pressure transduction [J].
Ben-Mansour, R. ;
Habib, M. A. ;
Khalifa, A. ;
Youcef-Toumi, K. ;
Chatzigeorgiou, D. .
COMPUTERS & FLUIDS, 2012, 57 :110-123
[5]   On the relationship between time and frequency domain methods in time delay estimation for leak detection in water distribution pipes [J].
Brennan, M. J. ;
Gao, Y. ;
Joseph, P. F. .
JOURNAL OF SOUND AND VIBRATION, 2007, 304 (1-2) :213-223
[6]   10 YEARS OF EXPERIENCE WITH LEAK DETECTION BY ACOUSTIC-SIGNAL ANALYSIS [J].
FUCHS, HV ;
RIEHLE, R .
APPLIED ACOUSTICS, 1991, 33 (01) :1-19
[7]   A model of the correlation function of leak noise in buried plastic pipes [J].
Gao, Y ;
Brennan, MJ ;
Joseph, PF ;
Muggleton, JM ;
Hunaidi, O .
JOURNAL OF SOUND AND VIBRATION, 2004, 277 (1-2) :133-148
[8]   On the effects of reflections on time delay estimation for leak detection in buried plastic water pipes [J].
Gao, Y. ;
Brennan, M. J. ;
Joseph, P. F. .
JOURNAL OF SOUND AND VIBRATION, 2009, 325 (03) :649-663
[9]   On the selection of acoustic/vibration sensors for leak detection in plastic water pipes [J].
Gao, Y ;
Brennan, MJ ;
Joseph, PF ;
Muggleton, JM ;
Hunaidi, O .
JOURNAL OF SOUND AND VIBRATION, 2005, 283 (3-5) :927-941
[10]   Acoustical characteristics of leak signals in plastic water distribution pipes [J].
Hunaidi, O ;
Chu, WT .
APPLIED ACOUSTICS, 1999, 58 (03) :235-254