Assessment of the dynamic thermal performance of massive buildings

被引:83
作者
Gagliano, A. [1 ]
Patania, F. [1 ]
Nocera, F. [1 ]
Signorello, C. [1 ]
机构
[1] Univ Catania, Dept Ind Engn, Catania, Italy
关键词
Natural ventilation; Thermal inertia; Time lag; Attenuation; Historical massive building; WALLS THERMOPHYSICAL PROPERTIES; NIGHT VENTILATION; DECREMENT FACTOR; TIME-LAG; COEFFICIENT CORRELATIONS; OFFICE BUILDINGS; SUMMER; DESIGN; SYSTEMS; INERTIA;
D O I
10.1016/j.enbuild.2013.12.060
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The aim of this paper is the evaluation of the thermal behavior of a massive building under the synergic combination of natural ventilation and thermal inertia. In particular, an experimental study has been carried out on Villa San Saverio, which is a massive historical building located in Catania (Italy), in order to characterize its thermal performance under dynamic conditions, and to evaluate the potential decrease of the indoor overheating by exploiting natural ventilation and limiting both internal and solar gains. The analysis of the transient behavior of this building permits to highlight the possibility of diversifying the time lag in relation to the wall orientation. A time lag of 12.00-14.00 h can be suggested for the walls due East. On the other hand, a time lag of around 8.00 h can be suggested to achieve the same result for the walls due West. Time lags higher than the values suggested above could be not fully functional, since delaying further the heat transfer from the wall to its inner surface, reduces the useful time for exploiting the cooling effect of the nocturnal ventilation. The results of both measurements and simulations indicate that high thermal inertia mass combined with natural ventilation prevents phenomena of overheating and ensures good comfort levels in occupied buildings, reducing the needs of cooling systems during summer period. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:361 / 370
页数:10
相关论文
共 34 条
[1]  
[Anonymous], 2008, DYN THERM CHAR CALC
[2]   Numerical computation of time lags and decrement factors for different building materials [J].
Asan, H .
BUILDING AND ENVIRONMENT, 2006, 41 (05) :615-620
[3]   Effects of Wall's thermophysical properties on time lag and decrement factor [J].
Asan, H ;
Sancaktar, YS .
ENERGY AND BUILDINGS, 1998, 28 (02) :159-166
[4]  
ASHRAE Task Group, 1975, PROC DET HEAT COOL L, P76
[5]   The influence of the external walls thermal inertia on the energy performance of well insulated buildings [J].
Aste, Niccolo ;
Angelotti, Adriana ;
Buzzetti, Michela .
ENERGY AND BUILDINGS, 2009, 41 (11) :1181-1187
[6]   The role of thermal mass on the cooling load of buildings. An overview of computational methods [J].
Balaras, CA .
ENERGY AND BUILDINGS, 1996, 24 (01) :1-10
[7]   Night ventilation for building cooling in summer [J].
Blondeau, P ;
Sperandio, M ;
Allard, F .
SOLAR ENERGY, 1997, 61 (05) :327-335
[8]   Energy and microclimatic performance of Mediterranean vernacular buildings: The Sassi district of Matera and the Trulli district of Alberobello [J].
Cardinale, Nicola ;
Rospi, Gianluca ;
Stefanizzi, Pietro .
BUILDING AND ENVIRONMENT, 2013, 59 :590-598
[9]   CONVECTIVE HEAT-EXCHANGE AT EXTERNAL SURFACE OF BUILDINGS [J].
COLE, RJ ;
STURROCK, NS .
BUILDING AND ENVIRONMENT, 1977, 12 (04) :207-214
[10]   New external convective heat transfer coefficient correlations for isolated low-rise buildings [J].
Emmel, Marcelo G. ;
Abadie, Marc O. ;
Mendes, Nathan .