A Low-Cost Evaluation and Correction Method for the Soluble Salt Components of the Insulator Contamination Layer

被引:19
作者
Cao, Bin [1 ]
Wang, Liming [1 ]
Yin, Fanghui [1 ]
机构
[1] Tsinghua Univ, Grad Sch Shenzhen, Shenzhen 518055, Peoples R China
关键词
Insulator contamination; ESDD; correction method; soluble salt components; PERFORMANCE;
D O I
10.1109/JSEN.2019.2902192
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Presently, equivalent salt deposit density (ESDD) is widely used by scientists and utility engineers to describe the site pollution severity due to its simple measurement procedure. When the contaminants are naturally accumulated on the insulator surface, some slightly soluble salts are only partially dissolved under saturated moisture condition. However, due to the large water consumption in the ESDD measurement process, these slightly soluble salts can be totally dissolved. Therefore, the measured ESDD may be higher than the actual pollution severity on the insulator surface. Thus, if using the measured ESDD to evaluate the flashover voltage of insulators in artificial pollution tests, the obtained results may be different from that of naturally contaminated insulators. This paper studied the dissolution amounts of highly and slightly soluble salts in the contamination layer by the ESDD measurement and compared them with a method proposed in this paper. The proposed method measures the surface conductivity of insulator under actual saturated moisture condition and can he used to correct the soluble salt components of natural contamination. Based on this method, a simple and novel device were also developed. The method proposed and device developed in this paper will be particularly useful for the selection and the design of insulators used in transmission lines.
引用
收藏
页码:5266 / 5273
页数:8
相关论文
共 30 条
[1]  
[Anonymous], 2016, 608154 IECTS
[2]  
[Anonymous], 2015, 61245 IEC TS
[3]  
[Anonymous], 2013, 60507 IEC
[4]  
[Anonymous], 2013, 41995 IEEE
[5]  
Chisholm W. A., 2016, SELECTING INSULATORS
[6]  
Chisholm W. A., 2013, P INMR WORLD C VANC, P208
[7]   ACCURATE MEASUREMENT OF LOW INSULATOR CONTAMINATION LEVELS [J].
CHISHOLM, WA ;
BUCHAN, PG ;
JARV, T .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (03) :1552-1557
[8]   Probes for spot measurement of surface conductivity on polluted insulators [J].
Chrzan, K. L. ;
Stec, C. ;
Farzaneh, M. .
IET SCIENCE MEASUREMENT & TECHNOLOGY, 2007, 1 (05) :295-300
[9]   Leakage Current on Porcelain and Silicone Insulators Under Sea or Light Industrial Pollution [J].
Chrzan, Krystian L. ;
Vosloo, Wallace L. ;
Holtzhausen, Jacobus P. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (03) :2051-2052
[10]  
Eish T. D., 1985, Conference Record of the 1985 International Conference on Properties and Applications of Dielectric Materials (Cat. No.85CH2115-4), P350