Time-Domain Transmission Line Fault Location Method With Full Consideration of Distributed Parameters and Line Asymmetry

被引:32
|
作者
Lu, Dayou [1 ,2 ,3 ,4 ]
Liu, Yu [1 ]
Liao, Qifeng [1 ]
Wang, Binglin [1 ]
Huang, Wentao [5 ,6 ]
Xi, Xinze [7 ,8 ]
机构
[1] ShanghaiTech Univ, Sch Informat Sci & Technol, Shanghai 201210, Peoples R China
[2] Chinese Acad Sci, Shanghai Adv Res Inst, Beijing, Peoples R China
[3] Chinese Acad Sci, Shanghai Inst Microsyst & Informat Technol, Beijing, Peoples R China
[4] Univ Chinese Acad Sci, Beijing, Peoples R China
[5] Shanghai Jiao Tong Univ SJTU, Dept Elect Engn, Shanghai 200240, Peoples R China
[6] Minist Educ, Key Lab Control Power Transmiss & Convers SITU, Shanghai 200240, Peoples R China
[7] Chongqing Univ, Sch Elect Engn, Chongqing 400044, Peoples R China
[8] Yunnan Power Grid Co Ltd, Elect Power Res Inst, Chongqing 400044, Peoples R China
基金
中国国家自然科学基金;
关键词
Fault location; Power transmission lines; Transmission line measurements; Mathematical model; Time-domain analysis; Transmission line matrix methods; Voltage measurement; Time-domain fault location; distributed transmission line model; line asymmetry; short data window; IEC; 61850; ALGORITHM;
D O I
10.1109/TPWRD.2020.2974294
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Accurate fault location reduces operating cost and outage time. This paper proposes a time-domain method to accurately locate faults in transmission lines, which only requires a very short data window (several milli-seconds) during faults. First, the voltage distribution through the line during faults is accurately obtained by solving the matrix form partial differential equations using the proposed numerical scheme. The proposed numerical scheme is mathematically validated for the transmission line fault location problem, with the optimal selection of time and distance intervals to ensure stability and minimum solution error. Afterwards, the fault location is obtained via the extremum value of the voltage distribution. The method fully considers distributed parameters as well as asymmetry of the line. Extensive numerical experiments validated that (a) the proposed numerical scheme demonstrates advantages towards other numerical schemes; (b) the proposed method presents higher fault location accuracy compared to the existing method, independent of fault types, locations and impedances; and (c) the fault location accuracy is not sensitive towards fault inception angles, loading conditions, measurement errors and parameter errors. The proposed method works with relatively low sampling rates (80 samples per cycle) and is compatible with IEC 61850 standard in present digital substations.
引用
收藏
页码:2651 / 2662
页数:12
相关论文
共 50 条
  • [41] Novel Method of Time-domain Fault Location for Wind Farm Double-circuit Transmission Lines
    Shu H.
    Deng Y.
    Cao P.
    Zhu M.
    Ma Y.
    An N.
    Dianwang Jishu/Power System Technology, 2023, 47 (04): : 1450 - 1459
  • [42] Parameter Identification Algorithm for Fault Location Based on Distributed Transmission Line model
    Kang, Xiaoning
    Jiale, Suonan
    Bo, Zhiqian
    Tang, Jian
    Jun, Qi
    2008 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-11, 2008, : 4098 - +
  • [43] Smart Fault Location and Fault Classification in Transmission Line
    Neethu, A. S.
    Angel, T. S.
    2017 IEEE INTERNATIONAL CONFERENCE ON SMART TECHNOLOGIES AND MANAGEMENT FOR COMPUTING, COMMUNICATION, CONTROLS, ENERGY AND MATERIALS (ICSTM), 2017, : 339 - 343
  • [44] Fault-Location Algorithms Without Utilizing Line Parameters Based on the Distributed Parameter Line Model
    Liao, Yuan
    Kang, Ning
    IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (02) : 579 - 584
  • [45] Improved Leap-frog Method for Time-domain Fault Location
    Dzafic, Izudin
    Jabr, Rabih A.
    JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2024, 12 (02) : 670 - 674
  • [46] Improved Leap-frog Method for Time-domain Fault Location
    Izudin Dafi
    Rabih AJabr
    Journal of Modern Power Systems and Clean Energy, 2024, 12 (02) : 670 - 674
  • [47] A Group of Single-Ended Time-Domain Line Fault Location Methods Using Breaker Operation Information
    Duan, Mengzhao
    Liu, Yu
    Liu, Ze
    Zou, Xinchen
    Guan, Zhongtao
    2023 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, PESGM, 2023,
  • [48] An adjoint variable method for time-domain transmission-line modeling with fixed structured grids
    Bakr, MH
    Nikolova, NK
    IEEE TRANSACTIONS ON MICROWAVE THEORY AND TECHNIQUES, 2004, 52 (02) : 554 - 559
  • [49] Time-domain method to calculate EMP coupling of buried cables based on transmission line model
    Engineering Institute of Engineering Corps, PLA Univ. of Sci. and Technol., Nanjing 210007, China
    Qiangjiguang Yu Lizishu, 2006, 7 (1163-1166):
  • [50] Guidelines for EMT Transmission Line Models for Time-Domain Protection Algorithms
    Vermunicht, Joachim
    Leterme, Willem
    Abedrabbo, Mudar
    Van Hertem, Dirk
    2023 IEEE BELGRADE POWERTECH, 2023,