Time-Domain Transmission Line Fault Location Method With Full Consideration of Distributed Parameters and Line Asymmetry

被引:32
|
作者
Lu, Dayou [1 ,2 ,3 ,4 ]
Liu, Yu [1 ]
Liao, Qifeng [1 ]
Wang, Binglin [1 ]
Huang, Wentao [5 ,6 ]
Xi, Xinze [7 ,8 ]
机构
[1] ShanghaiTech Univ, Sch Informat Sci & Technol, Shanghai 201210, Peoples R China
[2] Chinese Acad Sci, Shanghai Adv Res Inst, Beijing, Peoples R China
[3] Chinese Acad Sci, Shanghai Inst Microsyst & Informat Technol, Beijing, Peoples R China
[4] Univ Chinese Acad Sci, Beijing, Peoples R China
[5] Shanghai Jiao Tong Univ SJTU, Dept Elect Engn, Shanghai 200240, Peoples R China
[6] Minist Educ, Key Lab Control Power Transmiss & Convers SITU, Shanghai 200240, Peoples R China
[7] Chongqing Univ, Sch Elect Engn, Chongqing 400044, Peoples R China
[8] Yunnan Power Grid Co Ltd, Elect Power Res Inst, Chongqing 400044, Peoples R China
基金
中国国家自然科学基金;
关键词
Fault location; Power transmission lines; Transmission line measurements; Mathematical model; Time-domain analysis; Transmission line matrix methods; Voltage measurement; Time-domain fault location; distributed transmission line model; line asymmetry; short data window; IEC; 61850; ALGORITHM;
D O I
10.1109/TPWRD.2020.2974294
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Accurate fault location reduces operating cost and outage time. This paper proposes a time-domain method to accurately locate faults in transmission lines, which only requires a very short data window (several milli-seconds) during faults. First, the voltage distribution through the line during faults is accurately obtained by solving the matrix form partial differential equations using the proposed numerical scheme. The proposed numerical scheme is mathematically validated for the transmission line fault location problem, with the optimal selection of time and distance intervals to ensure stability and minimum solution error. Afterwards, the fault location is obtained via the extremum value of the voltage distribution. The method fully considers distributed parameters as well as asymmetry of the line. Extensive numerical experiments validated that (a) the proposed numerical scheme demonstrates advantages towards other numerical schemes; (b) the proposed method presents higher fault location accuracy compared to the existing method, independent of fault types, locations and impedances; and (c) the fault location accuracy is not sensitive towards fault inception angles, loading conditions, measurement errors and parameter errors. The proposed method works with relatively low sampling rates (80 samples per cycle) and is compatible with IEC 61850 standard in present digital substations.
引用
收藏
页码:2651 / 2662
页数:12
相关论文
共 50 条
  • [21] THE NEW METHOD OF TIME-DOMAIN ANALYSIS OF A PLANAR TRANSMISSION-LINE WITH DISCONTINUITY
    CHEN, L
    LI, SF
    INTERNATIONAL JOURNAL OF INFRARED AND MILLIMETER WAVES, 1991, 12 (11): : 1315 - 1320
  • [22] Unsynchronized Fault Location Independent on Line Parameters for Transmission Systems
    Khater, Wagdy M.
    Elkalashy, Nagy I.
    Kawady, Tamer A.
    Taalab, Abdel-Maksoud I.
    Lehtonen, Matti
    2014 IEEE PES INNOVATIVE SMART GRID TECHNOLOGIES CONFERENCE EUROPE (ISGT EUROPE), 2014,
  • [23] Transient formulation of lossy ground return parameters for time-domain transmission line analysis
    DAmore, M
    Sarto, MS
    IEEE 1996 INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY - EMC: SILICON TO SYSTEMS, SYMPOSIUM RECORD, 1996, : 213 - 218
  • [24] New time-domain method for locating arc fault in high voltage transmission line using one terminal data
    Shu, Hong-Chun
    Si, Da-Jun
    Ge, Yao-Zhong
    Chen, Xue-Yun
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2000, 20 (11): : 25 - 29
  • [25] Time Domain Fault Location Method Based on UHV Transmission Line Parameter Identification Using Two Terminal Data
    Zhang Yining
    Jiale, Suonan
    2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [27] A new transmission-line model for time-domain implementation
    Wilcox, DJ
    Condon, M
    COMPEL-THE INTERNATIONAL JOURNAL FOR COMPUTATION AND MATHEMATICS IN ELECTRICAL AND ELECTRONIC ENGINEERING, 1997, 16 (04) : 261 - +
  • [28] New transmission-line model for time-domain implementation
    COMPEL Int J Comput Math Electr Electron Eng, 4 (261-274):
  • [29] Multiconductor Transmission Line Scattering Parameters in Time Domain
    Wardzinska, Agnieszka
    Bandurski, Wojciech
    2014 IEEE 18TH WORKSHOP ON SIGNAL AND POWER INTEGRITY (SPI), 2014,
  • [30] Nonradiating sources in time-domain transmission-line theory
    Sihvola, A
    Kristensson, G
    Lindell, IV
    IEEE TRANSACTIONS ON MICROWAVE THEORY AND TECHNIQUES, 1997, 45 (12) : 2155 - 2159