Potential evaluation of water-cooled multiple screw chillers with serial water loops and development of ultra-efficient dual screw chillers

被引:5
|
作者
Wang, Chuang [1 ]
Wu, Xiaokun [2 ]
Sun, Shizhong [1 ]
Zhang, Zhiping [2 ]
Xing, Ziwen [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Peoples R China
[2] Gree Elect Appliances INC, State Key Lab Air Conditioning Equipment & Syst E, Zhuhai 519070, Peoples R China
基金
中国国家自然科学基金;
关键词
Multiple chillers; Screw compressors; Serial water loops; Ultra-efficient; REFRIGERATION SYSTEMS; GLOBAL OPTIMIZATION; CONTROL STRATEGY; HEAT-RECOVERY; HVAC SYSTEMS; ENERGY; TEMPERATURE; EXERGY; PUMP;
D O I
10.1016/j.applthermaleng.2022.118340
中图分类号
O414.1 [热力学];
学科分类号
摘要
Applying serial water loops in multiple screw chillers has the potential to improve the COP of screw chillers above 7.0. However, the maximum potential of this method hasn't been identified and the ultra-efficient target hasn't been achieved until now. Therefore, an energy and exergy analysis is performed on the water-cooled multiple chillers with serial water loops in this paper to recognize their maximum potential. Analysis results show that the water-cooled multiple screw chillers with serial water loops have the maximum potential to increase COP by 26.02% and exergy efficiency by approximately 22% relative to the single screw chiller under the normal operating condition. Adding one chiller based on the single chiller system could increase the COP by 11.38%, and it is not suggested to design multiple chillers with more than four chillers owing to the reduced additional improvement in COP with the increasing number of chillers. Moreover, both condensers and both evaporators should be designed with the equal area of heat exchange, respectively, aiming to set the equal temperature difference through both evaporators and both condensers. On basis of analysis results, the ultra efficient dual screw chillers were developed and tested. The COP and IPLV of the chillers reached 7.22 and 9.50, which were higher than the minimum allowable value of the first-order energy efficiency for water chillers by 20.3% and 26.67%.
引用
收藏
页数:10
相关论文
共 5 条
  • [1] Formulation of Coefficient of Performance Characteristics of Water-cooled Chillers and Evaluation of Composite COP for Combined Chillers
    Yamamoto, Toru
    Hayama, Hirofumi
    Hayashi, Takao
    ENERGIES, 2020, 13 (05)
  • [2] Flow measurement uncertainty quantification for building central cooling systems with multiple water-cooled chillers using a Bayesian approach
    Sun, Shaobo
    Wang, Shengwei
    Shan, Kui
    APPLIED THERMAL ENGINEERING, 2022, 202
  • [3] Pre-industrial development and experimental characterization of new air-cooled and water-cooled ammonia/lithium nitrate absorption chillers
    Zamora, Miguel
    Bourouis, Mahmoud
    Coronas, Alberto
    Valles, Manel
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 45 : 189 - 197
  • [4] Detection and Diagnosis of Multiple-Dependent Faults (MDFDD) of Water-Cooled Centrifugal Chillers Using Grey-Box Model-Based Method
    Dou, Hongwen
    Zmeureanu, Radu
    ENERGIES, 2023, 16 (01)
  • [5] Model Unraveling the Ultra-Efficient Multi-Stage Flow-Through Anodes for Water Purification Application: Development of Design and Evaluation
    Chen, Min
    Hu, Chengzhi
    Liu, Huijuan
    Qu, Jiuhui
    ACS ES&T ENGINEERING, 2023, 3 (06): : 787 - 797