Analysis of the Thermal Storage Performance of a Radiant Floor Heating System with a PCM

被引:23
|
作者
Park, JinChul [1 ]
Kim, TaeWon [2 ]
机构
[1] Chung Ang Univ, Dept Architecture, Seoul 156756, South Korea
[2] Chung Ang Univ, Grad Sch, Dept Architecture Engn, Seoul 156756, South Korea
基金
新加坡国家研究基金会;
关键词
phase change material; radiant floor heating system; thermal storage; mock-up test; SHAPE-STABILIZED PCM;
D O I
10.3390/molecules24071352
中图分类号
Q5 [生物化学]; Q7 [分子生物学];
学科分类号
071010 ; 081704 ;
摘要
This study first reviewed previous studies on floor heating systems based on the installation of a phase change material (PCM) and the current status of technical developments and found that PCM-based research is still in its infancy. In particular, the improvement of floor heat storage performance in indoor environments by combining a PCM with existing floor structures has not been subject to previous research. Thus, a PCM-based radiant floor heating system that utilizes hot water as a heat source and can be used in conjunction with the widespread wet construction method can be considered novel. This study found the most suitable PCM melting temperature for the proposed PCM-based radiant floor heating system ranged from approximately 35 degrees C to 45 degrees C for a floor thickness of 70 mm and a PCM thickness of 10 mm. Mock-up test results, which aimed to assess the performance of the radiant floor heating system with and without the PCM, revealed that the PCM-based room was able to maintain a temperature that was 0.2 degrees C higher than that of the room without the PCM. This was due to the rise in temperature caused by the PCM's heat storage capacity and the emission of waste heat that was otherwise lost to the underside of the hot water pipe when the PCM was not present.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] Thermal comfort analysis of PCM electric floor radiant heating system
    Chen Qi-zhen
    Feng Guo-hui
    Niu Run-ping
    Li Guo-jian
    Li Wen-jie
    Wang Jian-hui
    JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY, 2007, 14 : 111 - 114
  • [2] Thermal performance of a radiant floor heating system with different heat storage materials and heating pipes
    Zhou, Guobing
    He, Jing
    APPLIED ENERGY, 2015, 138 : 648 - 660
  • [3] Analysis of Thermal Performance and Energy Saving Potential by PCM Radiant Floor Heating System based on Wet Construction Method and Hot Water
    Baek, Sanghoon
    Kim, Sangchul
    ENERGIES, 2019, 12 (05):
  • [4] Radiant heating floors with PCM bands for thermal energy storage: A numerical analysis
    Gonzalez, B.
    Prieto, M. M.
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2021, 162
  • [5] Model establishment and operation optimization of the casing PCM radiant floor heating system
    Lu, Shilei
    Gao, Jingxian
    Tong, Haojie
    Yin, Shuai
    Tang, Xiaolei
    Jiang, Xiangyang
    ENERGY, 2020, 193 : 1208 - 1224
  • [6] A study on the thermal performance simulation integrated with hydronic analysis in radiant floor heating system
    Yang, K. W.
    Jung, H.
    Rhee, K. N.
    Ryu, S. R.
    Yeo, M. S.
    Kim, K. W.
    FIRST INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT, PROCEEDINGS VOLS 1-3, 2008, : 1911 - 1918
  • [7] Optimizing the axis ratio of elliptical PCM encasement for enhanced thermal performance in radiant floor heating systems
    Wang, Zhenyu
    Gao, Weijun
    Sun, Jian
    Gao, Yanna
    SCIENTIFIC REPORTS, 2025, 15 (01):
  • [8] Influence of hot water pipe position on the performance of radiant floor heating systems integrated with PCM
    Wang, Zhenyu
    Gao, Weijun
    Gao, Yanna
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 61
  • [9] A thermal analysis of a radiant floor heating system using SERI-RES
    Chun, WG
    Jeon, MS
    Lee, YS
    Jeon, HS
    Lee, TK
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1999, 23 (04) : 335 - 343
  • [10] Thermal performance of new hybrid solar energy-phase change storage-floor radiant heating system
    Zhang, Ye
    Chen, Chao
    Jiao, Hao
    Wang, Wanjiang
    Shao, Zongyi
    Qi, DianWei
    Wang, Rong
    8TH INTERNATIONAL COLD CLIMATE HVAC CONFERENCE, 2016, 146 : 88 - 98