Airborne transmission of exhaled droplet nuclei between occupants in a room with horizontal air distribution

被引:43
作者
Ai, Z. T. [1 ]
Huang, T. [1 ]
Melikov, A. K. [1 ]
机构
[1] Tech Univ Denmark, Dept Civil Engn, Int Ctr Indoor Environm & Energy, Lyngby, Denmark
关键词
Airborne transmission; Cross infection; Ventilation; Air distribution; Breathing manikin; PERSONALIZED VENTILATION; CROSS-INFECTION; PERFORMANCE EVALUATION; DYNAMIC PROPERTIES; HOSPITAL WARD; TRACER GAS; EXPOSURE; RISK; ENVIRONMENT; POLLUTANTS;
D O I
10.1016/j.buildenv.2019.106328
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study examines the characteristics of the airborne spread of exhaled droplet nuclei between two persons indoors with horizontal airflow distribution in a full-scale test room. Two breathing thermal manikins were used to simulate an infected and an exposed person. Tracer gas (N2O) was added to the airstream exhaled by the infected manikin. The tracer gas concentrations in the air inhaled by the exposed manikin and in the room ventilation exhaust were continuously monitored using both slow and fast instruments. The independent variables included the separation distance between the simulated persons, the positioning of the persons, the location of the persons in relation to the supply diffuser, the room air temperature, and the installation height and configuration of the air supply and exhaust diffusers. Special attention was paid to exploring the dependence of exposure risk on the distance between the two manikins under different directions of indoor airflow. Air supplied horizontally to the breathing zone intensified the mixing between the exhaled air and the room air, which reduced the exposure risk of persons in close proximity and flattened the risk-distance curves. The highly dynamic dispersion of exhaled air and thus the homogenization of tracer gas concentration in room air considerably reduced the importance of the positioning of the infected and exposed persons. The exposure risk between closely located persons increased when the interaction between the supply flow and the exhaled flow decreased due to an increased supply air temperature, an augmented size of supply air diffuser or decreased height above the floor of the diffusers.
引用
收藏
页数:11
相关论文
共 41 条
  • [1] Airborne spread of expiratory droplet nuclei between the occupants of indoor environments: A review
    Ai, Z. T.
    Melikov, A. K.
    [J]. INDOOR AIR, 2018, 28 (04) : 500 - 524
  • [2] Airborne transmission between room occupants during short-term events: Measurement and evaluation
    Ai, Zhengtao
    Hashimoto, Kaho
    Melikov, Arsen K.
    [J]. INDOOR AIR, 2019, 29 (04) : 563 - 576
  • [3] A comparison between tracer gas and aerosol particles distribution indoors: The impact of ventilation rate, interaction of airflows, and presence of objects
    Bivolarova, M.
    Ondracek, J.
    Melikov, A.
    Zdimal, V.
    [J]. INDOOR AIR, 2017, 27 (06) : 1201 - 1212
  • [4] Dispersal of exhaled air and personal exposure in displacement ventilated rooms
    Bjorn, E
    Nielsen, PV
    [J]. INDOOR AIR, 2002, 12 (03) : 147 - 164
  • [5] Bolashikov Z.D., 2011, P IND AIR AUST TX
  • [6] Wearable personal exhaust ventilation: Improved indoor air quality and reduced exposure to air exhaled from a sick doctor
    Bolashikov, Zhecho D.
    Barova, Maria
    Melikov, Arsen K.
    [J]. SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2015, 21 (08) : 1117 - 1125
  • [7] Exposure of health care workers and occupants to coughed airborne pathogens in a double-bed hospital patient room with overhead mixing ventilation
    Bolashikov, Zhecho D.
    Melikov, Arsen K.
    Kierat, Wojciech
    Popiolek, Zbigniew
    Brand, Marek
    [J]. HVAC&R RESEARCH, 2012, 18 (04): : 602 - 615
  • [8] Center for Disease Control and Prevention (CDC), DIS COND
  • [9] Performance of personalized ventilation in conjunction with mixing and displacement ventilation
    Cermak, R
    Melikov, AK
    Forejt, L
    Kovar, O
    [J]. HVAC&R RESEARCH, 2006, 12 (02): : 295 - 311
  • [10] Protection of occupants from exhaled infectious agents and floor material emissions in rooms with personalized and underfloor ventilation
    Cermak, Radim
    Melikov, Arsen K.
    [J]. HVAC&R RESEARCH, 2007, 13 (01): : 23 - 38