Condition Assessment of Cellulosic Part in Power Transformer Insulation using Transfer Function Zero of Modified Debye Model

被引:52
作者
Baral, A. [1 ]
Chakravorti, S. [1 ]
机构
[1] Jadavpur Univ, Dept Elect Engn, Kolkata 700032, W Bengal, India
关键词
Conventional Debye model; modified Debye model; transfer function; aging; paper moisture content; power transformer; OIL-PAPER INSULATION; DIELECTRIC RESPONSE; FREQUENCY-DOMAIN; SPECTROSCOPY; SYSTEM;
D O I
10.1109/TDEI.2014.004517
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Analysis of Polarization-Depolarization Current, recorded from high voltage oil-paper insulation using insulation model is common among researchers. It is reported that paper insulation of power transformers undergoes non-uniform aging. Unlike Conventional Debye Model (CDM), Modified Debye Model (MDM) is capable of modeling such non-uniform aging. However, factors like insulation geometry affect the values of the MDM branch parameters. Therefore, model parameterized using data obtained from one insulation system finds limited use in assessing the condition of a different transformer, even with similar loading history and power rating. The present paper shows that a performance parameter, which is less sensitive to insulation geometry, can be evaluated from Transfer Function, TFM(s) of MDM. The parameter is the zero Z(1) of TFM(s) which is located farthest away from the origin in the Left Half Plane of s-plane. The capability of Z(1) as an insulation condition sensitive parameter is first tested on laboratory samples and then on data recorded from several real life power transformers. Results obtained for these transformers show that there is a good correlation between magnitude of Z(1) and paper moisture content obtained from Frequency Domain Spectroscopy (FDS) using IDAX 300.
引用
收藏
页码:2028 / 2036
页数:9
相关论文
共 24 条
[1]  
[Anonymous], 1998, IEEE C EL INS DIEL P, DOI DOI 10.1109/ceidp.1998.734015
[2]  
[Anonymous], 2010, P IEEE PES GEN M PES
[3]   Assessment of Non-Uniform Aging of Solid Dielectric using System Poles of a Modified Debye Model for Oil-paper Insulation of Transformers [J].
Baral, A. ;
Chakravorti, S. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (05) :1922-1933
[4]   A Modified Maxwell Model for Characterization of Relaxation Processes Within Insulation System having Non-uniform Aging Due to Temperature Gradient [J].
Baral, A. ;
Chakravorti, S. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (02) :524-534
[5]  
Bernstein D. S., 2005, MATRIX MATH THEORY F
[6]  
Bognar A., 1991, 7 INT S HV ENG, P9
[7]  
Der Houhanessian V, 1998, CONFERENCE RECORD OF THE 1998 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, P28, DOI 10.1109/ELINSL.1998.704641
[8]  
DerHouhanessian V, 1996, CONFERENCE RECORD OF THE 1996 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, P47, DOI 10.1109/ELINSL.1996.549280
[9]   On the Frequency Domain Dielectric Response of Oil-paper Insulation at Low Temperatures [J].
Fofana, I. ;
Hemmatjou, H. ;
Meghnefi, F. ;
Farzaneh, M. ;
Setayeshmehr, A. ;
Borsi, H. ;
Gockenbach, E. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (03) :799-807
[10]  