Short-Term State Forecasting-Aided Method for Detection of Smart Grid General False Data Injection Attacks

被引:153
作者
Zhao, Junbo [1 ,2 ]
Zhang, Gexiang [1 ]
La Scala, Massimo [3 ]
Dong, Zhao Yang [4 ]
Chen, Chen [5 ]
Wang, Jianhui [5 ]
机构
[1] Southwest Jiaotong Univ, Sch Elect Engn, Chengdu 610031, Peoples R China
[2] Virginia Polytech Inst & State Univ, Northern Virginia Ctr, Bradley Dept Elect Comp Engn, Falls Church, VA 22043 USA
[3] Politecn Bari, Dept Elect Engn & Comp Sci, I-70125 Bari, Italy
[4] Univ Sydney, Sch Elect & Informat Engn, Sydney, NSW 2006, Australia
[5] Argonne Natl Lab, Argonne, IL 60439 USA
基金
中国国家自然科学基金;
关键词
False data injection attack; state estimation; cyber security; smart grid;
D O I
10.1109/TSG.2015.2492827
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Successful detection of false data injection attacks (FDIAs) is essential for ensuring secure power grids operation and control. First, this paper extends the approximate dc model to a more general linear model that can handle both super-visory control and data acquisition and phasor measurement unit measurements. Then, a general FDIA based on this model is derived and the error tolerance of such attacks is discussed. To detect such attacks, a method based on short-term state forecasting considering temporal correlation is proposed. Furthermore, a statistics-based measurement consistency test method is presented to check the consistency between the forecasted measurements and the received measurements. This measurement consistency test is further integratedwith infinity-norm and L-2-norm-basedmeasurement residual analysis to construct the proposed detection metric. The proposed detector addresses the shortcoming of previous detectors in terms of handling critical measurements. Besides, the removal problem of attacked measurements, which may cause the system to become unobservable, is addressed effectively by the proposed method through forecasted measurements. Numerical tests on IEEE 14-bus and 118-bus test systems verify the effectiveness and performance of the proposed method.
引用
收藏
页码:1580 / 1590
页数:11
相关论文
共 35 条
[1]  
Abur A., 2004, POWER SYSTEM STATE E
[2]  
[Anonymous], C371182005 IEEE
[3]  
[Anonymous], 1977, Journal of the Royal Statistical Society, Series C (Applied Statistics), DOI DOI 10.2307/2346884
[4]  
Ashok A., 2012, IEEE PES Meeting, P1
[5]  
Blood EA, 2008, IEEE POW ENER SOC GE, P5601
[6]  
Bobba R. B., 2010, 1 WORKSH SEC CONTR S, P1
[7]  
Bonneville Power Administration, 2011, WIND GEN TOT LOAD BP
[8]   An Estimation Fusion Method for Including Phasor Measurements Into Power System Real-Time Modeling [J].
Costa, Antonio Simoes ;
Albuquerque, Andre ;
Bez, Daniel .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (02) :1910-1920
[9]   Coordinated Data-Injection Attack and Detection in the Smart Grid [J].
Cui, Shuguang ;
Han, Zhu ;
Kar, Soummya ;
Kim, Tung T. ;
Poor, H. Vincent ;
Tajer, Ali .
IEEE SIGNAL PROCESSING MAGAZINE, 2012, 29 (05) :106-115
[10]   State Estimation and Voltage/VAR Control in Distribution Network With Intermittent Measurements [J].
Deshmukh, Siddharth ;
Natarajan, Balasubramaniam ;
Pahwa, Anil .