Moisture buffering capacity of hygroscopic building materials: Experimental facilities and energy impact

被引:282
作者
Osanyintola, Olalekan F. [1 ]
Simonson, Carey J. [1 ]
机构
[1] Univ Saskatchewan, Dept Mech Engn, Saskatoon, SK S7N 5A9, Canada
基金
加拿大创新基金会; 加拿大自然科学与工程研究理事会;
关键词
moisture buffering capacity; energy savings; experimental facility; uncertainty; indoor air quality; convective transfer coefficients; spruce plywood;
D O I
10.1016/j.enbuild.2006.03.026
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Research into dynamic moisture storage in hygroscopic building materials has renewed interest in the moisture buffering capacity of building materials and shown the potential for these materials to improve indoor humidity, thermal comfort and indoor air quality in buildings. This paper complements previous research by estimating the effect of hygroscopic materials on energy consumptions in buildings. The results show that it may be possible to reduce heating and cooling energy consumption by up to 5% and 30%, respectively, when applying hygroscopic materials with well-controlled HVAC systems. The paper also describes two different experimental facilities that can be used to measure accurately the moisture buffering capacity of hygroscopic building materials. These facilities provide different convective transfer coefficients between the hygroscopic material and ambient air, ranging from natural convection in small, sealed jars to fully developed laminar and turbulent forced convection. The paper presents a numerical model and property data for spruce plywood which will be used in a companion paper [O.F. Osanyintola, R Talukdar, C.J. Simonson, Effect of initial conditions, boundary conditions and thickness on the moisture buffering capacity of spruce plywood, Energy and Buildings (2006), doi:10.1016/j.enbuild.2006.03.024.] to provide additional insight into the design of an experiment to measure the moisture buffering capacity of hygroscopic materials. (C) 2006 Elsevier B.V. All rights reserved.
引用
收藏
页码:1270 / 1282
页数:13
相关论文
共 48 条
[1]  
ANDRESEN I, 1992, ASHRAE TRAN, V98, P910
[2]  
[Anonymous], 2003, C518 ASTM
[3]   Heat recovery and floating condensing in supermarkets [J].
Arias, J ;
Lundqvist, P .
ENERGY AND BUILDINGS, 2006, 38 (02) :73-81
[4]  
*ASHRAEN I, 2004, 55 ASHRAE ANSI
[5]  
ASTM, 2005, E96E96M ASTM
[6]  
*ASTM, 1985, E104 ASTM
[7]   Real-time determination of optimal indoor-air condition for thermal comfort, air quality and efficient energy usage [J].
Atthajariyakul, S ;
Leephakpreeda, T .
ENERGY AND BUILDINGS, 2004, 36 (07) :720-733
[8]  
BRAUN JE, 1990, ASHRAE TRAN, V96, P876
[9]  
*CEN, 1988, 1752 CEN CR EUR COMM
[10]   Assessing the thermal performance of an emergency shelter system [J].
Crawford, C ;
Manfield, P ;
McRobie, A .
ENERGY AND BUILDINGS, 2005, 37 (05) :471-483