Back-to-back capacitor energization transients mitigation: Comparison of pre-insertion inductors versus surge reactors on a 46 kV subtransmission system

被引:2
|
作者
Bohmann, LJ
Demler, JR
Barna, BA
机构
[1] Michigan Technological University, Houghton, MI
[2] MCL Industries, Oneida, WI
[3] Consumers Power Company, Jackson, MI
来源
ELECTRIC MACHINES AND POWER SYSTEMS | 1997年 / 25卷 / 09期
关键词
D O I
10.1080/07313569708955794
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Two devices that are used to reduce back-to-back; capacitor bank energization transients, pre-insertion inductors and surge reactors, are investigated in this paper. The Alternative Transients Program (ATP) was used to develop a computer model of a 46-kV system, A parametric study, varying the switched capacitor size and the system strength, was completed to determine the effectiveness of the two methods, Pre-insertion inductors reduced the peak inrush current better than the surge reactors, However, both of these devices generated peak overvoltages greater than the case containing neither of them. The optimum inductor size is highly system dependent, A thorough study of the system should be completed before the choice is made to use pre-insertion inductors or surge reactors.