Behaviour of Cellulosic Oil Impregnated Insulation Material at High Frequency Stress Used for High Voltage Solid State Transformer Applications

被引:0
|
作者
Schueller, M. [1 ]
Schmitt, P. [2 ]
Kaminskis, U. [2 ]
Christen, R. [1 ]
Smajic, J. [1 ]
机构
[1] Univ Appl Sci Rapperswil, Rapperswil, Switzerland
[2] Weidmann Elect Technol AG, Chiasso, Switzerland
来源
PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 2 | 2020年 / 599卷
关键词
High voltage high frequency breakdown; Breakdown mechanism at high frequency; Oil paper insulation; Solid state transformer;
D O I
10.1007/978-3-030-31680-8_20
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Solid state transformers (SSTs) are a new type of transformers where power electronics and conventional transforming elements are combined into one. The basic principle is that the voltage gets converted into the kHz range before it is transformed to another voltage level. The main advantage of this technology is the size of the transformer - due to the used higher frequency the transformer core and thus the whole apparatus can be built smaller than traditional 50/60 Hz power transformers. Currently there are no oil impregnated cellulosic insulation systems available for high-voltage high-frequency applications. This is partly because the exact breakdown mechanism at high frequency (HF) stress is still unclear and partly because long-term behavior of cellulosic insulation systems under HF-stress is unknown. The main goal of this publication is to provide new experiments and data to contribute on the research of the HF breakdown mechanism in oil impregnated cellulosic insulation systems. For this purpose breakdown experiments on oil impregnated paper samples were conducted at frequencies of 50 Hz, 20 kHz and 40 kHz with unipolar voltage pulses. Tests were performed at 20 degrees C and 90 degrees C in synthetic ester fluid Midel 7131. As voltage source a special self-developed pulsed HF generator was used that provides high-voltage high-frequency voltage up to 6.5 kV between 50 Hz and 40 kHz. As expected, decrease in breakdown voltage with increasing frequency could be shown. But more important, the findings presented in this paper surprisingly also suggest that contrary to most literature not heating due to increased polarization losses is the main responsible breakdown mechanism at high frequency stress.
引用
收藏
页码:194 / 202
页数:9
相关论文
共 50 条
  • [41] Investigation of the effects of mixed electric field stress on high voltage transformer insulation
    Seyfi, Pourya
    Zahedi, Saeed
    Shojaei, Hojat
    Ghomi, Hamid
    ELECTRICAL ENGINEERING, 2022, 104 (04) : 2267 - 2279
  • [42] A Modular SiC High-Frequency Solid-State Transformer for Medium-Voltage Applications: Design, Implementation, and Testing
    Dong, Dong
    Agamy, Mohammed
    Bebic, Jovan Z.
    Chen, Qin
    Mandrusiak, Gary
    IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2019, 7 (02) : 768 - 778
  • [43] Study and Implementation of High Frequency Cast Resin Transformer Applied for Medium-Voltage Solid-State Transformer
    Chen, Kuan-Ting
    Chen, Jiann-Fuh
    Wang, Tsung-Jen
    Liao, Hsuan
    2021 IEEE INTERNATIONAL FUTURE ENERGY ELECTRONICS CONFERENCE (IFEEC), 2021,
  • [44] Testing of insulation systems with respect to high-frequency voltage stress
    Paede, M
    Pfeiffer, W
    Plessow, R
    EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2002, 12 (05): : 337 - 345
  • [45] Physics-Based Design Optimization of High Frequency Transformers for Solid State Transformer Applications
    Olowu, Temitayo O.
    Jafari, Hassan
    Moghaddami, Masood
    Sarwat, Arif, I
    2019 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING, 2019,
  • [46] BEHAVIOR OF IMPREGNATED COMPOSITE INSULATION UNDER HIGH-VOLTAGE AT VERY LOW-FREQUENCY
    FANG, JW
    GZYLEWSKI, J
    RAGHUVEER, MR
    KUFFEL, E
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (09): : 3158 - 3165
  • [47] EPOXY-RESIN-IMPREGNATED PAPER INSULATION SYSTEM FOR ULTRA-HIGH-VOLTAGE APPLICATIONS
    ISOGAI, T
    IKEMOTO, N
    INOUE, T
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1971, EI 6 (02): : 94 - &
  • [48] The Effects of PWM With High dv/dt on Partial Discharge and Lifetime of Medium-Frequency Transformer for Medium-Voltage (MV) Solid State Transformer Applications
    Agarwal, Rachit
    Li, Hui
    Guo, Zhehui
    Cheetham, Peter
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2023, 70 (04) : 3857 - 3866
  • [49] Accurate Equivalent Circuit Modeling of a Medium-Voltage and High-Frequency Coaxial Winding DC-link Transformer for Solid State Transformer Applications
    Baek, Seunghun Samuel
    Cougo, Bernardo
    Bhattacharya, Subhashish
    Ortiz, Gabriel
    2012 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2012, : 1439 - 1446
  • [50] Compact high voltage, high peak power, high frequency transformer for converter type modulator applications
    Reghu, T.
    Mandloi, V.
    Shrivastava, Purushottam
    REVIEW OF SCIENTIFIC INSTRUMENTS, 2016, 87 (04):