Behaviour of Cellulosic Oil Impregnated Insulation Material at High Frequency Stress Used for High Voltage Solid State Transformer Applications

被引:0
|
作者
Schueller, M. [1 ]
Schmitt, P. [2 ]
Kaminskis, U. [2 ]
Christen, R. [1 ]
Smajic, J. [1 ]
机构
[1] Univ Appl Sci Rapperswil, Rapperswil, Switzerland
[2] Weidmann Elect Technol AG, Chiasso, Switzerland
来源
PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 2 | 2020年 / 599卷
关键词
High voltage high frequency breakdown; Breakdown mechanism at high frequency; Oil paper insulation; Solid state transformer;
D O I
10.1007/978-3-030-31680-8_20
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Solid state transformers (SSTs) are a new type of transformers where power electronics and conventional transforming elements are combined into one. The basic principle is that the voltage gets converted into the kHz range before it is transformed to another voltage level. The main advantage of this technology is the size of the transformer - due to the used higher frequency the transformer core and thus the whole apparatus can be built smaller than traditional 50/60 Hz power transformers. Currently there are no oil impregnated cellulosic insulation systems available for high-voltage high-frequency applications. This is partly because the exact breakdown mechanism at high frequency (HF) stress is still unclear and partly because long-term behavior of cellulosic insulation systems under HF-stress is unknown. The main goal of this publication is to provide new experiments and data to contribute on the research of the HF breakdown mechanism in oil impregnated cellulosic insulation systems. For this purpose breakdown experiments on oil impregnated paper samples were conducted at frequencies of 50 Hz, 20 kHz and 40 kHz with unipolar voltage pulses. Tests were performed at 20 degrees C and 90 degrees C in synthetic ester fluid Midel 7131. As voltage source a special self-developed pulsed HF generator was used that provides high-voltage high-frequency voltage up to 6.5 kV between 50 Hz and 40 kHz. As expected, decrease in breakdown voltage with increasing frequency could be shown. But more important, the findings presented in this paper surprisingly also suggest that contrary to most literature not heating due to increased polarization losses is the main responsible breakdown mechanism at high frequency stress.
引用
收藏
页码:194 / 202
页数:9
相关论文
共 50 条
  • [21] Dielectric Breakdown Characteristics of Epoxy Resin Induced by High Frequency Electric Stress Used in Solid State Transformer
    Wang, Weiwang
    Wang, Xin
    He, Jiefeng
    Liu, Ying
    Li, Shengtao
    PROCEEDINGS OF THE 2020 3RD IEEE INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD 2020), 2020, : 162 - 165
  • [22] Insulation Structure Analysis of High-Frequency and High-Voltage Rectifier Transformer
    Wang, Yanan
    Huang, Yibin
    Xiao, Dengming
    Qin, Songlin
    ICPADM 2009: PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2009, : 154 - 157
  • [23] Design of a High-Voltage-Insulation and High-Efficiency Medium Frequency Transformer
    Zhu, Shilong
    Shao, Shuai
    Awais, Muhammad
    Zhang, Junming
    IECON 2020: THE 46TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2020, : 4091 - 4095
  • [24] A High-Frequency Semi Co-Axial Transformer With High Insulation Voltage
    Heuvelmans, Matthijs
    2017 19TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE'17 ECCE EUROPE), 2017,
  • [25] Development of a Medium Voltage, High Power, High Frequency Four-Port Solid State Transformer
    El Shafei, Ahmad
    Ozdemir, Saban
    Altin, Necmi
    Jean-Pierre, Garry
    Nasiri, Adel
    CES TRANSACTIONS ON ELECTRICAL MACHINES AND SYSTEMS, 2022, 6 (01) : 95 - 104
  • [26] Development of a Medium Voltage, High Power, High Frequency Four-Port Solid State Transformer
    Ahmad El Shafei
    Saban Ozdemir
    Necmi Altin
    Garry Jean-Pierre
    Adel Nasiri
    CES Transactions on Electrical Machines and Systems, 2022, 6 (01) : 95 - 104
  • [27] High frequency voltage oscillation in transformer windings and electrical breakdown properties of interturn insulation immersed in oil at VFT voltage
    Nakanishi, K
    Fujita, S
    Kurita, H
    Kishi, A
    Shibuya, Y
    IEEE 1997 ANNUAL REPORT - CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS I AND II, 1997, : 490 - 493
  • [28] Bidirectional Converter with High Frequency Isolation Feasible to Solid State Transformer Applications
    Mazza, Luan Carlos
    Oliveira, Demercil
    Antunes, Fernando
    Dias, Antonio
    da Silva, Jose Cleomon
    Freitas, Alisson
    2016 18TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE'16 ECCE EUROPE), 2016,
  • [29] Study of Degradation Phenomena of Solid Insulation used in Extra High Voltage Cable under Alternating Voltage Stress
    Karmakar, Subrata
    2018 IEEE 2ND INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD), 2018,
  • [30] Algorithm for Determining the State of Impregnated Paper Insulation of High-Voltage Cables
    Sidorova, Anna
    Semenov, Dmitry
    Cheremukhin, Artem
    Astakhova, Tatyana
    INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2019, 20 (04):