Behaviour of Cellulosic Oil Impregnated Insulation Material at High Frequency Stress Used for High Voltage Solid State Transformer Applications

被引:0
|
作者
Schueller, M. [1 ]
Schmitt, P. [2 ]
Kaminskis, U. [2 ]
Christen, R. [1 ]
Smajic, J. [1 ]
机构
[1] Univ Appl Sci Rapperswil, Rapperswil, Switzerland
[2] Weidmann Elect Technol AG, Chiasso, Switzerland
来源
PROCEEDINGS OF THE 21ST INTERNATIONAL SYMPOSIUM ON HIGH VOLTAGE ENGINEERING, VOL 2 | 2020年 / 599卷
关键词
High voltage high frequency breakdown; Breakdown mechanism at high frequency; Oil paper insulation; Solid state transformer;
D O I
10.1007/978-3-030-31680-8_20
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Solid state transformers (SSTs) are a new type of transformers where power electronics and conventional transforming elements are combined into one. The basic principle is that the voltage gets converted into the kHz range before it is transformed to another voltage level. The main advantage of this technology is the size of the transformer - due to the used higher frequency the transformer core and thus the whole apparatus can be built smaller than traditional 50/60 Hz power transformers. Currently there are no oil impregnated cellulosic insulation systems available for high-voltage high-frequency applications. This is partly because the exact breakdown mechanism at high frequency (HF) stress is still unclear and partly because long-term behavior of cellulosic insulation systems under HF-stress is unknown. The main goal of this publication is to provide new experiments and data to contribute on the research of the HF breakdown mechanism in oil impregnated cellulosic insulation systems. For this purpose breakdown experiments on oil impregnated paper samples were conducted at frequencies of 50 Hz, 20 kHz and 40 kHz with unipolar voltage pulses. Tests were performed at 20 degrees C and 90 degrees C in synthetic ester fluid Midel 7131. As voltage source a special self-developed pulsed HF generator was used that provides high-voltage high-frequency voltage up to 6.5 kV between 50 Hz and 40 kHz. As expected, decrease in breakdown voltage with increasing frequency could be shown. But more important, the findings presented in this paper surprisingly also suggest that contrary to most literature not heating due to increased polarization losses is the main responsible breakdown mechanism at high frequency stress.
引用
收藏
页码:194 / 202
页数:9
相关论文
共 50 条
  • [1] Development of a Pulsed High Frequency Source for Testing Cellulosic Insulation Material for High Voltage Solid State Transformer Applications
    Schueller, M.
    Schmitt, Ph
    Jaufer, S.
    Krause, Ch
    Gatti, G.
    Christen, R.
    Bucher, M. K.
    Smajic, J.
    2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [2] Estimation of the water content in high voltage oil-impregnated transformer insulation
    Shkolnik, A.
    2006 IEEE 24TH CONVENTION OF ELECTRICAL & ELECTRONICS ENGINEERS IN ISRAEL, 2006, : 363 - 367
  • [3] Investigation on the high frequency, high voltage insulation properties of mineral transformer-oil
    Nagel, M.
    Leibfried, T.
    2006 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2006, : 226 - 228
  • [4] A High Power High Frequency Transformer Design for Solid State Transformer Applications
    El Shafei, Ahmad
    Ozdemir, Saban
    Altin, Necmi
    Jean-Pierre, Garry
    Nasiri, Adel
    2019 8TH INTERNATIONAL CONFERENCE ON RENEWABLE ENERGY RESEARCH AND APPLICATIONS (ICRERA 2019), 2019, : 904 - 909
  • [5] Insulation Design on High-Frequency Transformer for Solid-State Transformer
    Li, Zheqing
    Hsieh, Yi-Hsun
    Li, Qiang
    Lee, Fred C.
    Zhao, Chunyang
    2021 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2021, : 1149 - 1155
  • [6] Design Considerations of High Voltage and High Frequency Transformer for Solid State Transformer Application
    Baek, Seunghun
    Du, Yu
    Wang, Gangyao
    Bhattacharya, Subhashish
    IECON 2010: 36TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2010,
  • [7] A High-Frequency PCB-Winding Transformer Design with Medium Voltage Insulation for Solid-State Transformer
    Li, Zheqing
    Jin, Feng
    Hsieh, Yi-Hsun
    Li, Qiang
    2023 IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION, APEC, 2023, : 1536 - 1542
  • [8] High-Frequency Transformer Design With Medium-Voltage Insulation for Resonant Converter in Solid-State Transformer
    Li, Zheqing
    Hsieh, Eric
    Li, Qiang
    Lee, Fred C.
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2023, 38 (08) : 9917 - 9932
  • [9] HIGH INSULATION VOLTAGE GATE-DRIVER APPLIED TO A SOLID STATE TRANSFORMER
    Cazakevicius, Fabricio E.
    Quevedo, Josemar O.
    Beltrame, Rafael C.
    Pinheiro, Jose Renes
    2015 IEEE 13TH BRAZILIAN POWER ELECTRONICS CONFERENCE AND 1ST SOUTHERN POWER ELECTRONICS CONFERENCE (COBEP/SPEC), 2015,
  • [10] High Frequency Transformers for Solid-State Transformer Applications
    Santos, Nuno
    Chaves, Miguel
    Gamboa, Paulo
    Cordeiro, Armando
    Santos, Nelson
    Pinto, Sonia Ferreira
    APPLIED SCIENCES-BASEL, 2023, 13 (12):