A quasi-transient model of a transcritical carbon dioxide direct-expansion ground source heat pump for space and water heating

被引:23
作者
Eslami-Nejad, Parham [1 ]
Ouzzane, Mohamed [1 ]
Aidoun, Zine [1 ]
机构
[1] Nat Resources Canada, CanmetENERGY, Varennes, PQ J3X 1S6, Canada
关键词
Theoretical modeling; Ground source heat pump; Carbon dioxide; Direct expansion; Geothermal borehole; AIR-SOURCE; SYSTEM; PERFORMANCE; BOREHOLE;
D O I
10.1016/j.applthermaleng.2015.07.058
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, a theoretical quasi-transient model is developed for detailed simulations of a carbon dioxide (CO2) direct-expansion ground source heat pump (DX-GSHP). This model combines a transient analytical model for the ground, steady-state numerical models for the borehole and the gas cooler, as well as several thermodynamic models for the remaining components of a conventional heat pump, organized in interacting subroutines to form a powerful simulation tool. Extensive validation combining experimental data and CFD-generated results was performed for the borehole before the tool was used to simulate a practical application case. Performance is investigated for a system satisfying both space heating and domestic hot water requirements of a typical single family detached home in a cold climate region. The variation of different system parameters is also evaluated in this study. It is shown that CO2 DX-GSHPs can offer relatively efficient and stable performance for integrated water and space heating applications. Furthermore, the importance of an accurate geothermal borehole sizing is highlighted for the DX-CO2 heat pump systems. It is shown that, due to changes in the system working conditions, the total borehole length is not linearly correlated with the heat pump energy consumption and other parameters such as heat pump coefficient of performance and pressure drop in ground heat exchangers. Results showed that increasing the total borehole length of an optimum design (reference case study) by 25% decreases the total annual energy consumption by only 6%. However, reducing total borehole length of the reference case by 25% increases the total annual energy consumption by 10%. Crown Copyright (C) 2015 Published by Elsevier Ltd. All rights reserved.
引用
收藏
页码:259 / 269
页数:11
相关论文
共 35 条
  • [1] Exergy analysis of a two-stage ground source heat pump with a vertical bore for residential space conditioning under simulated occupancy
    Ally, Moonis R.
    Munk, Jeffrey D.
    Baxter, Van D.
    Gehl, Anthony C.
    [J]. APPLIED ENERGY, 2015, 155 : 502 - 514
  • [2] Parametric study on the performance of a direct-expansion geothermal heat pump using carbon dioxide
    Austin, Brian T.
    Sumathy, K.
    [J]. APPLIED THERMAL ENGINEERING, 2011, 31 (17-18) : 3774 - 3782
  • [3] Beauchamp Benoit., 2013, Journal of Energy and Power Engineering, V7, P237
  • [4] Bertsch S., 2005, 8 IHA HEAT PUMP C LA
  • [5] Bredesen AM, 1997, REFR SCI T, V1997, P35
  • [6] In-tube cooling heat transfer of supercritical carbon dioxide. Part 1. Experimental measurement
    Dang, C
    Hihara, E
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2004, 27 (07) : 736 - 747
  • [7] Modeling of a two-phase CO2-filled vertical borehole for geothermal heat pump applications
    Eslami-Nejad, Parham
    Ouzzane, Mohamed
    Aidoun, Zine
    [J]. APPLIED ENERGY, 2014, 114 : 611 - 620
  • [8] Modified heat transfer equation for in-tube supercritical CO2 cooling
    Fang, Xiande
    Xu, Yu
    [J]. APPLIED THERMAL ENGINEERING, 2011, 31 (14-15) : 3036 - 3042
  • [9] Experimental analysis of a direct expansion geothermal heat pump in heating mode
    Fannou, Jean-Louis
    Rousseau, Clement
    Lamarche, Louis
    Stanislaw, Kajl
    [J]. ENERGY AND BUILDINGS, 2014, 75 : 290 - 300
  • [10] A comparative performance study of a direct expansion geothermal evaporator using R410A and R407C as refrigerant alternatives to R22
    Fannou, Jean-Louis Comlan
    Rousseau, Clement
    Lamarche, Louis
    Kajl, Stanislaw
    [J]. APPLIED THERMAL ENGINEERING, 2015, 82 : 306 - 317