H8 Inverter to Reduce Leakage Current in Transformerless Three-Phase Grid-Connected Photovoltaic systems

被引:104
作者
Rahimi, Ramin [1 ]
Farhangi, Shahrokh [1 ]
Farhangi, Babak [2 ]
Moradi, Gholam Reza [1 ]
Afshari, Ehsan [3 ]
Blaabjerg, Frede [4 ]
机构
[1] Univ Tehran, Sch Elect & Comp Engn, Tehran 14395515, Iran
[2] Current Ways Inc, Los Angeles, CA 91303 USA
[3] Northeastern Univ, Dept Elect & Comp Engn, Boston, MA 02115 USA
[4] Aalborg Univ, Dept Energy Technol, DK-9220 Aalborg, Denmark
关键词
Common-mode voltage; grid-connected inverter; leakage current; stray capacitor; transformerless inverter; COMMON-MODE VOLTAGE; MODULATION TECHNIQUES; MULTILEVEL INVERTER;
D O I
10.1109/JESTPE.2017.2743527
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, a three-phase grid-connected photovoltaic (PV) topology (named H8) is proposed to address the leakage current issue. AC common-mode voltage and earth leakage current cause problems in the transformerless grid-connected PV systems. Leakage current increases the distortion of the current injected into the grid and the losses, also it generates unwanted radiated and conducted electromagnetic interference. The voltage source full-bridge inverter, which is also known as B6-type converter is widely used for three-phase PV systems. The B6-type inverter suffers from the leakage current, which limits its application to transformerless grid-connected PV systems. The proposed H8 topology reduces the leakage current as well as common-mode voltage variations through the separation of the PV array from the grid during the zero voltage states. Through analysis, simulations, and experimental results, a comparison between the proposed topology and the conventional B6-type topology is performed. Results validate the performance improvements of H8 inverter in terms of leakage current and total harmonic distortion of the output currents injected into the grid. Experimental results are presented for a 2-kW grid-connected PV system.
引用
收藏
页码:910 / 918
页数:9
相关论文
共 30 条
[1]  
Afshari E., 2017, IEEE T IND ELECTRON, V46, P1
[2]  
Afshari E, 2015, 2015 IEEE CONFERENCE ON ENERGY CONVERSION (CENCON), P413, DOI 10.1109/CENCON.2015.7409580
[3]   Neutral Point Clamped MOSFET Inverter With Full-Bridge Configuration for Nonisolated Grid-Tied Photovoltaic System [J].
Anandababu, Chakravartula ;
Fernandes, Baylon G. .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2017, 5 (01) :445-457
[4]   Modulation for Three-Phase Transformerless Z-Source Inverter to Reduce Leakage Currents in Photovoltaic Systems [J].
Bradaschia, Fabricio ;
Cavalcanti, Marcelo C. ;
Ferraz, Pedro E. P. ;
Neves, Francisco A. S. ;
dos Santos, Euzeli C., Jr. ;
da Silva, Joao H. G. M. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (12) :5385-5395
[5]   Modulation Techniques to Eliminate Leakage Currents in Transformerless Three-Phase Photovoltaic Systems [J].
Cavalcanti, Marcelo C. ;
de Oliveira, Kleber C. ;
de Farias, Alexandre M. ;
Neves, Francisco A. S. ;
Azevedo, Gustavo M. S. ;
Camboim, Felipe C. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2010, 57 (04) :1360-1368
[6]   Common-Mode Filter Design for a Transformerless ZVS Full-Bridge Inverter [J].
Chen, Yenan ;
Xu, Dehong ;
Xi, Jiangbei .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2016, 4 (02) :405-413
[7]  
Freddy TKS, 2013, IEEE CONF CLEAN ENER, P277, DOI 10.1109/CEAT.2013.6775640
[8]   Modulation Techniques to Reduce Leakage Current in Three-Phase Transformerless H7 Photovoltaic Inverter [J].
Freddy, Tan Kheng Suan ;
Rahim, Nasrudin A. ;
Hew, Wooi-Ping ;
Che, Hang Seng .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (01) :322-331
[9]   Transformerless inverter for single-phase photovoltaic systems [J].
Gonzalez, Roberto ;
Lopez, Jesus ;
Sanchis, Pablo ;
Marroyo, Luis .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2007, 22 (02) :693-697
[10]   Three-Phase CH7 Inverter With a New Space Vector Modulation to Reduce Leakage Current for Transformerless Photovoltaic Systems [J].