Accelerated aging test to determine the replacement criterion of distribution surge arresters

被引:0
|
作者
Kim, JY [1 ]
Kim, CY [1 ]
Song, IK [1 ]
Moon, JD [1 ]
机构
[1] Korea Elect Power Corp, KEPRI, Deajon 305380, South Korea
来源
2001 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION, VOLS 1 AND 2: DEVELOPING NEW PERSPECTIVES | 2001年
关键词
ZnO; surge arresters; leakage current; accelerated aging; thermal runaway; resistive leakage current;
D O I
10.1109/TDC.2001.971339
中图分类号
TP3 [计算技术、计算机技术];
学科分类号
0812 ;
摘要
This paper provides the results of accelerated aging test of 18kV ZnO surge arresters to investigate the leakage current characteristics. It was impossible to establish the replacement criterion for field operating surge arresters because conventional aging test was only focused on the aging of ZnO elements. In general it is possible to replace the aged arresters before the failure in the field using the leakage current measurement because it must be increased by the aging. But we can not use this method because we don't know the characteristics of the surge arresters installed in the field. Therefore in this paper we applied operating voltage and accelerating cycle which consists of temperature and humidity to the arresters, Then we measured the variation of total and resistive leakage current and found out the characteristics of the aged surge arresters.
引用
收藏
页码:793 / 796
页数:4
相关论文
共 50 条
  • [1] An investigation of aging characteristics of polymer housed distribution surge arresters by accelerated aging test
    Kim, Juyong
    Park, Chulbae
    Jung, Yeunha
    Song, Ilkeun
    2008 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2008, : 593 - 596
  • [2] Multistress accelerated aging of polymer housed surge arresters under simulated coastal Florida conditions
    Sundararajan, R
    Soundarajan, E
    Mohammed, A
    Graves, J
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (01) : 211 - 226
  • [3] PERFORMANCE OF DISTRIBUTION SURGE ARRESTERS.
    Lat, M.V.
    Kortschinski, J.
    Research Review - Ontario Hydro, 1980, (01): : 25 - 30
  • [4] Effect of Artificial Aging on Polymeric Surge Arresters and Polymer Insulators for Electricity Distribution Networks
    Ferreira, Carlos A.
    Coser, E.
    Angelini, Joceli M. G.
    Rossi, Jose A. D.
    Martinez, Manuel L. B.
    POLIMEROS-CIENCIA E TECNOLOGIA, 2011, 21 (05): : 436 - 442
  • [5] New Test Standard for MO Surge Arresters
    Richter, Bernhard
    2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2014, : 1194 - 1197
  • [6] Multistress aging tests of polymer housed surge arresters
    Kester, JJ
    Miller, DR
    Benna, SJ
    Steinbrecher, BT
    IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (02) : 446 - 452
  • [7] A FAST TRANSIENT TEST MODULE FOR ZNO SURGE ARRESTERS
    HADDAD, A
    NAYLOR, P
    GERMAN, DM
    WATERS, RT
    MEASUREMENT SCIENCE AND TECHNOLOGY, 1995, 6 (05) : 560 - 570
  • [8] The Effect of Cable Aging on Surge Arresters Designed by Genetic Algorithm
    Zielinski, Dariusz
    Grzechca, Damian
    APPLIED SCIENCES-BASEL, 2023, 13 (20):
  • [9] Determination of the Discharge Current on Distribution Network Surge Arresters
    de Salles, C.
    Picanco, A. F.
    Martinez, M. L. B.
    de Oliveira, H. R. P. M.
    2009 IEEE BUCHAREST POWERTECH, VOLS 1-5, 2009, : 3030 - +
  • [10] Behaviour of insulators and surge arresters at Glogow pollution test station
    Chrzan, KL
    Haddad, A
    UPEC 2004: 39th International Universitities Power Engineering Conference, Vols 1-3, Conference Proceedings, 2005, : 193 - 196